Chapter 10 Using microSD Cards
Figure 17 - Recipe Function Block Timing Diagram
Quickstart Projects for Data
Log and Recipe Function
Blocks
The following sample quickstart projects provide step-by-step instructions on
how to use the Data Log and Recipe function blocks in the Connected
Components Workbench software to generate and manage your recipe files
and data logs.
Disable(0)
Enable(1)
Disable(0)
Enable(1)
Disable(0)
Idle(0)
Busy(1)
Succeed(2)
Idle(0)
Busy(1)
Error(3)
Idle(0)
Enable(1)
Status(0)
IMPORTANT
RCP Function Block Execution
• There are three possible states for Recipe function block: Idle, Busy,
Complete (Complete with Succeed and Complete with Error)
• For one Recipe function block execution, the typical status starts from Idle
then Busy and finishes with Complete. To trigger another function block
execution, the status needs to go back to Idle first.
• Idle status changes to Busy status only when Enable input signal is in rising
edge. Complete status enters Idle status when Enable input signal is on
Disable status.
• RWFlag, CfgId, and RcpName input parameters are only sampled at Enable
input parameter's rising edge when a new function block execution starts.
During function block execution, input parameters of RWFlag, CfgId, and
RcpName are locked and any changes are ignored.
• When the function block execution finishes, the function block status
changes from Busy to Complete. At this stage, if input Enable is False,
function block status changes to Idle after staying as Complete for exactly
one scan time. Otherwise, function block status remains Complete until input
Enable changes to False.
• Recipe function block file name supports a maximum of 30 bytes in length,
and only supports upper and lower case letters Aa…Zz, numbers 0…9 and
underscore (_).
• The RcpName input parameter does not allow file extension (for example,
.txt) to be added to its value. The recipe data file is written to the microSD
card with the .txt extension.
• There are separators in between every data variable in the recipe data file
that is defined during configuration in Connected Components Workbench
software. Redundant tab, space, carriage return, and line feed characters
are strictly not allowed.
Supported Data Types for Data Log and Recipe Function Blocks on
• Double quotes are not allowed within a string in a recipe file.