Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Chapter 10 Using microSD Cards
Figure 16 - Data Log Function Block Timing Diagram
Disable(0)
Enable(1)
Disable(0)
Enable(1)
Disable(0)
Idle(0)
Busy(1)
Succeed(2)
Idle(0)
Busy(1)
Error(3)
Idle(0)
Enable(1)
Status(0)
IMPORTANT
Data Log Function Block Execution
• There are three possible states for the Data Log function block: Idle, Busy,
and Complete (which includes Complete with Succeed and Complete with
Error).
• For one Data Log function block execution, the typical status starts from Idle,
then Busy and finishes with Complete. To trigger another function block
execution, the status needs to go back to Idle first.
• Idle status changes to Busy status only when Enable input signal is in rising
edge. Complete status enters Idle status when Enable input signal is Disable
status only.
• TSEnable and CfgId input parameters are only sampled at Enable input
parameter's rising edge when a new function block execution starts. During
function block execution, the input parameters of TSEnable and CfgId are
locked and any changes are ignored.
• When execution completes, the status changes from Busy to Complete. At
this stage, if input Enable is False, status changes to Idle after indicating
Complete for exactly one scan time. Otherwise function block status is kept
as Complete until input Enable changes to False.
• The data log file can only be created by the DLG instruction block. The
Connected Components Workbench software can only upload and delete the
data log file.
• There are separators in between every data variable in the data file that is
defined during configuration in the Connected Components Workbench
software.
Supported Data Types for Data Log and Recipe Function Blocks on
• Data variable values are sampled when data logging function block is in Busy
state. However, data logging file is only created when data logging function
block is in Complete state.
Table 38 - Supported Data Types for Data Log and Recipe Function Blocks
Data Type
Description
Example Format in Output Data Log File
BOOL
(1)
Logical Boolean with values
TRUE and FALSE
0: FALSE
1: TRUE)
SINT
Signed 8-bit integer value
-128, 127
INT
Signed 16-bit integer value
-32768, 32767
DINT
Signed 32-bit integer value
-2147483648, 2147483647
LINT
Signed 64-bit integer value
-9223372036854775808, 9223372036854775807