186
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Appendix A Specifications
Isolation voltage
250V (continuous), Reinforced Insulation Type, Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, Inputs to Aux and Network, 3250V
DC Outputs to Aux and Network, Inputs to Outputs
50V (continuous), Reinforced Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network, Inputs to
Outputs
Pilot duty rating
C300, R150
—
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication
General Specifications — Micro830 10-point Controllers (Continued)
Attribute
2080-LC30-10QWB
2080-LC30-10QVB
Inputs — Micro830 10-point Controllers
Attribute
2080-LC30-10QWB, 2080-LC30-10QVB
High-Speed DC Input (Inputs 0…3)
Standard DC Input (inputs 4 and higher)
Number of Inputs
4
2
Input group to backplane isolation Verified by one of the following dielectric tests: 1,414V DC for 2 s
75V DC working voltage (IEC Class 2 reinforced insulation)
Voltage category
24V DC sink/source
Off-state voltage, max
5V DC
On-state voltage, nom
24V DC
On-state voltage range
16.8…26.4V DC @ 65 °C (149 °F)
16.8…30.0V DC @ 30 °C (86 °F)
10…26.4V DC @ 65 °C (149 °F)
10…30.0V DC @ 30 °C (86 °F)
Off-state current, max
1.5 mA
On-state current, min
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
8.8 mA @ 24V DC
8.5 mA @ 24V DC
On-state current, max
12.0 mA @ 30V DC
Nominal impedance
3 k
Ω
3.74 k
Ω
IEC input compatibility
Type 3
AC input filter setting
8 ms for all embedded inputs
(In the Connected Components Workbench software, go to the Embedded I/O configuration window to reconfigure the filter setting for each
input group)
Isolated AC Inputs — Micro830 10-point Controllers
Attribute
2080-LC30-10QWB, 2080-LC30-10QVB (Inputs 0…3)
On-state voltage, nom
12/24V AC @ 50/60 Hz
Off-state voltage, min
4V AC @ 50/60Hz
Operating frequency, nom
50/60 Hz