160
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Chapter 10 Using microSD Cards
data log directories. The following sections include information on how to
configure the ConfigMeFirst.txt properly.
Power-up Settings in ConfigMeFirst.txt
On power-up, the controller reads and carries out configuration settings
described in the ConfigMeFirst.txt file. However, the UPD setting also takes
effect when the microSD card is inserted. The configuration settings for the
ConfigMeFirst.txt file are shown in the following table.
IMPORTANT
The Micro800 controller reports a major fault when project backup does not
succeed because the memory card size is exceeded.
ConfigMeFirst.txt Configuration Settings
Setting
Takes Effect On...
Description
Firmware update settings
[FWFILE]
Power-up
File path location of the firmware revision on the microSD
card. The default location is in the following format:
firmware\<catalog number>\<filename of firmware>
[FWDOWN]
Power-up
Sets whether to upgrade or downgrade the controller
firmware from the current revision.
0 = Upgrade firmware; 1 = Downgrade firmware
IMPORTANT:
Firmware Upgrade will happen if [FWFILE]
setting points to a newer revision of firmware file compared
to current firmware in the controller, irrespective of
[FWDOWN] setting.
Controller settings
[PM]
Power-up
Power up and switch to PROGRAM mode.
[CF]
Power-up
Power up and attempt to clear fault.
Project settings
[BKD = My Proj1]
Power-up
Power up and save the controller project into backup
directory,
My Proj1\USERPRJ. Require extra power cycle to clear
existing fault first using [CF] setting or other means.
[RSD = MyProj2]
Power-up
Power up and read the project from restore directory
MyProj2\USERPRJ into controller. Require extra power cycle
to clear existing fault first using [CF] setting or other means.
This setting overwrites UPD (or its default) load always or
load on error restore function.
[UPD = My Proj]
Power-up and
Insertion
For normal usage of backup and restore (that is, through
Connected Components Workbench software, Load Always,
or Load on Memory Error settings), set the user project
directory name. For example, My Proj, during power-up or
when the microSD card is inserted.
This directory is also used by data logging and recipe
function.
Network settings
[ESFD]
Power-up
Embedded Serial Factory Defaults.
Power up and revert embedded serial comms to factory
defaults.
[IPA = xxx.xxx.xxx.xxx]
Power-up
Power up and set IP address to xxx
(must be numbers only).
[SNM = xxx.xxx.xxx.xxx]
Power-up
Power up and set subnet mask to xxx
(must be numbers only).