50
Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 5
Installing Input and Output Power Wiring
Installing Wiring from the
Power Module Output
Terminals to the Motor
Use the following steps to connect the AC output power wiring from the power
module to the motor.
1.
Turn off, lock out, and tag the input power to the drive. Wait 5 minutes.
2.
Remove the input wiring panel and drill the required number of openings
for the wiring. See
.
3.
Connect the three-phase AC output power motor leads to the power
module busbars labeled U, V, and W. See
and
.
4.
Tighten the three-phase AC output power terminals:
• Frame 3 – M10 Class 8.8 or 3/8 in. Grade 5 fastener. Tighten to
40N•m (30 lb•ft).
• Frame 4 – M12 Class 8.8 or 1/2 in. Grade 5 fastener. Tighten to
100N•m (75 lb•ft).
Table 5 - Recommended Minimum Motor Lead Wire Size
IMPORTANT
The total motor lead length must not exceed 76 m (250 ft). See
recommended minimum motor lead wire sizes.
Power Module Model Number
Minimum Motor Lead Wire Size
(1)
(1) Motor lead wiring
must
comply with all local and national codes.
LF200460AAR
2 x 2/0 AWG
LF200608CCR
2 x 250 MCM
LF200900CCR
4 x 250 MCM
LF201215CCR
4 x 250 MCM
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......