210
Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 10
Troubleshooting the Drive
SW OverCurrent
36
The drive output current has exceeded the software current
limit.
Check for excess load, improper DC boost setting. DC brake volts set too
high.
UnderVoltage
4
DC bus voltage fell below the minimum value of: 305V DC
input.
Enable/disable with inverter Fault Config 1(238).
Monitor the incoming AC line for low voltage or power interruption.
UserSet1 Chksum
101
The checksum read from the user set does not match the
checksum calculated.
These faults can be cleared by writing a nonzero value to
inverter Save To User Set (199).
Re-save user set using inverter Save To User Set (199).
UserSet2 Chksum
102
UserSet3 Chksum
103
Table 22 - Fault Descriptions and Corrective Actions (Frame 4) (Continued)
Fault
No
.
Ty
pe
Description
Action
Table 23 - Fault Names Cross-Referenced by Fault Number
No.
(1)
Fault
No.
(1)
Fault
No.
(1)
Fault
2
Auxiliary Input
48
Params Defaulted
214
Reactor Temp
3
Power Loss
63
Shear Pin
215
Rctfr HW Unused
(3)
4
UnderVoltage
64
Drive Overload
216
Rctfr Gnd Fault
5
OverVoltage
70
HW Fault
217
Rctfr Base Temp
7
Motor Overload
71...76
Port 1...6 Adapter
218
Rctfr IGBT Temp
8
Invtr Base Temp
77
IR Volts Range
219
Rctfr IT Overld
9
Invtr IGBT Temp
78
FluxAmpsRef Rang
220
Rctfr I2T Overld
12
HW OverCurrent
79
Excessive Load
221
Ride Thru Abort
13
Ground Fault
80
AutoTune Aborted
222
High AC Line
14
Inv Shunt Trip
81...86
Port 1...6 DPI Loss
223
Low DC Bus
15
Hi Vdc Shunt
87
IXo VoltageRange
224
Rctfr Over Volt
18
Invtr I Offset U
100
Parameter Chksum
225
Input I Imbalance
19
Invtr I Offset V
101
UserSet1 Chksum
226
Input V Imbalance
20
Invtr I Offset W
102
UserSet2 Chksum
227
AC Line Lost
21
Rctfr I Offset R
103
UserSet3 Chksum
228
Line Feq Lost
22
Rctfr I Offset S
104
Pwr Brd Chksum1
229
Rctfr Checksum
23
Rctfr I Offset T
105
Pwr Brd Chksum2
230
Invtr HW Unk
24
Decel Inhibit
106
Incompat MCB-PB
231
Rctfr HW Unk
25
OverSpeed Limit
107
Replaced MCB-PB
232
Rctfr Not OK
29
Analog In Loss
120
I/O Mismatch
(3)
233
Precharge Closed
30
NTC Demux Fail
(2)
121
I/O Comm Loss
234
Precharge Opened
31
Inv Temp Switch
(2)
122
I/O Board Fail 3
235
Rctfr Pwr Board
33
Auto Rstrt Tries
123
Invtr Unk IO Brd
(2)
236
Rctfr IO Board
35
Current Fbk Lost
197...199
Invtr Dsat U-, V-, W-
(2)
237
Not At Voltage
36
SW OverCurrent
200...202
Invtr Dsat U, V, W
(3)
238
Rctfr Not Login
37
Motor I Imbalance
200...202
Invtr Dsat U+, V+, W+
(2)
239
Power Phased ACB
38
Phase U to Grnd
203...205
Invtr Over Cur U, V, W
240
Rctfr Gate Kill
(2)
39
Phase V to Grnd
206
Invtr HW Unused
(3)
241...243
Rctfr Dsat R-, S-, T-
(2)
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......