170
Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9
Parameter Descriptions
The base frequency for the motor, for the purpose of calculating the optimal DC
bus voltage.
This parameter is only used when Vdc Optimize (102) is set to
Enabled
.
See the description of Max Motor Volts (107) for a full description of how this
parameter is used.
Base Motor Freq (109) normally has the same value as inverter parameter Motor
NP Hertz (43).
Voltage Major Loop integral gain.
Voltage Major Loop proportional gain.
Current Minor Loop integral gain.
109
Base Motor Freq
Range:
5.0...400.0 [0.1 Hz]
Default:
60.0
Access:
0
Path:
Dynamic Control > Load Limits
See also:
102, 104, 107, 108, inverter 43
110
VML Ki
Range:
0...65535
Default:
Based on drive size
Access:
0
Path:
Dynamic Control > Regulator Tuning
See also:
111
VML Kp
Range:
0...65535
Default:
Based on drive size
Access:
0
Path:
Dynamic Control > Regulator Tuning
See also:
112
CML Ki
Range:
0...65535
Default:
Based on drive size
Access:
0
Path:
Dynamic Control > Regulator Tuning
See also:
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......