Rockwell Automation Publication D2-3518-4 - January 2020
169
Parameter Descriptions
Chapter 9
If the input current is greater than Input Load Amps (106), then the rectifier I
2
T
overload percentage (as seen in Rctfr I
2
T Overld, rectifier parameter 21) counts
up.
If Rctfr I
2
T Overld (21) reaches 100%, the Rectfier I
2
T Overload fault
(fault 220) occurs.
If Vdc Optimize (102) is set to
Enabled
, the DC bus voltage
generated by the
rectifier
while the rectifier or the entire drive is running is calculated based on a
combination of the DC bus level necessary to provide the motor voltage required
by the inverter and the measured line-to-line voltage of the AC line.
Max Motor Volts (107) is the maximum RMS motor voltage requirement that
can be calculated by the Vdc Optimize function.
The Vdc Optimize function calculates the motor voltage requirement as Max
Motor Volts (107) when the output (motor) frequency is equal to Base Motor
Freq (109), and from that point linearly varies the calculated motor voltage
requirement down to 0 Volts at 0 Hz output frequency. If the output frequency is
greater than Base Motor Frequency (109), the calculated motor voltage
requirement is limited to Max Motor Volts (107).
If Vdc Optimize (102) is set to
Enabled
, Max Motor Volts (107) should have the
same value as inverter parameter Maximum Voltage (54).
If Vdc Optimize (102) is set to
Disabled
, Max Motor Volts (107) is not used.
The maximum frequency that can be commanded by the inverter.
This value is used for calculating drive output frequency as part of the
determination of the optimal DC bus voltage to command.
Max Motor Freq (108) should have the same value as inverter parameter
Maximum Freq (55). This parameter is only used if Vdc Optimize (102) is set to
Enabled
.
107
Max Motor Volts
Range:
60.0...480.0V AC [0.1V AC]
Default:
480.0
Access:
0
Path:
Dynamic Control > Load Limits
See also:
102, 104, 108, 109, inverter 54
108
Max Motor Freq
Range:
5.0...400.0 [0.1 Hz]
Default:
130.0
Access:
0
Path:
Dynamic Control > Load Limits
See also:
102, 104, 107, 109, inverter 55
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......