Rockwell Automation Publication D2-3518-4 - January 2020
201
Troubleshooting the Drive
Chapter 10
I/O Comm Loss
121
Loss of communication to inverter standard I/O board.
1. Cycle power.
2. If fault persists, verify connection between inverter I/O board and inverter
control board.
3. If fault still persists, replace inverter standard I/O board.
4. If fault still persists, replace inverter control board.
I/O Mismatch
120
Incorrect inverter I/O board identified.
Restore inverter I/O board to original configuration, or If new configuration is
desired, reset fault.
Incompat MCB-PB
106
Drive rating information stored on the inverter power
board is incompatible with the inverter Control board
firmware.
Load compatible version files into inverter.
Input I Imbalance
225
Input phase current imbalance exceeded limits.
1. Fault 225 can occur if rectifier Line I Imbalance (22) is greater than rectifier I
Imbalance Lmt (62) for longer than the time in rectifier I Imbalance Time
(63). Verify that rectifier parameters 62 and 63 have the correct values. If this
is the cause of the fault 225, fault 225 should also appear in the rectifier fault
queue (rectifier parameters 243...250).
2. Check for line voltage imbalance. A line voltage imbalance can cause a line
current imbalance. See rectifier Line V Imbalance (23).
3. Check for existence of rectifier instantaneous overcurrent (IOC) faults
(rectifier faults 12, 211, 212, 213) in rectifier fault queue (rectifier parameters
243...250). Short duration events on AC line can cause rectifier overcurrents,
which can be reported as drive fault 225. See description of rectifier IOC Redir
Time (rectifier 300) and IOC Redir Max (rectifier 301).
4. Check for existence of rectifier Line V Imbal OL fault (rectifier fault 16) in
rectifier fault queue (rectifier parameters 243...250). This rectifier fault can
be caused by short duration AC line events and is reported as drive fault 225.
5. Check rectifier current feedback wiring and signal path, which includes the
rectifier power board and the rectifier control board.
Input V Imbalance
226
Rectifier Line V Imbalance (23) exceeded rectifier
V Imbalance Lmt (60) for more than the time in rectifier
V Imbalance Time (61).
1. Check for problem in input power distribution.
2. Check line voltage feedback wiring and signal path: includes line
synchronization board, AC Line I/O board, Rectifier control board.
Inv Shunt Trip
14
Drive has activated the shunt trip because the inverter
firmware has commanded it. This can be caused by the
detection of a motor-side (inverter) ground fault
(fault 13), or by the user writing a
1
to bit 0 of inverter
Appl Digital Out (inverter 30).
1. See table entry for Ground Fault (13).
2. Determine why a
1
was written to bit 0 of inverter Appl Digital Out
(inverter 30).
Invtr Base Temp
8
Measured temperature of one of the inverter IGBT
modules exceeded limit.
Check for proper temperature and flow rate of coolant.
Invtr Dsat
U, V, W
200
201
202
High current was detected in an IGBT.
1. Check for loose connection in IGBT wire harness.
2. Check IGBTs.
Invtr Gate Kill
207
Inverter gate kill contact is open.
Close gate kill contact.
Invtr HW Unk
230
Inverter section of power structure hardware reported
unexpected fault.
1. Verify connection between inverter control board and inverter power board.
2. If fault persists, replace inverter power board.
3. If fault still persists, replace inverter control board.
Invtr HW Unused
206
Inverter section of power structure hardware reported
unexpected fault.
1. Verify connection between inverter control board and inverter power board.
2. If fault persists, replace inverter power board.
3. If fault still persists, replace inverter control board.
Invtr I Offset
U, V, W
18
19
20
An inverter current feedback offset calculated at drive
start was out of range.
Check inverter current feedback signal path.
Invtr IGBT Temp
9
Calculated inverter IGBT junction temperature has
exceeded its rated maximum. See inverter diagnostic
parameter 2, IGBT Junct Temp.
Check for proper temperature and flow rate of coolant.
Invtr Over Cur
U, V, W
203
204
205
High current was detected in an IGBT.
1. Verify proper motor data is entered.
2. Reduce current limit.
Table 21 - Fault Descriptions and Corrective Actions (Frame 3) (Continued)
Fault
No
.
Ty
pe
Description
Action
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......