Chapter 9
Parameter Descriptions
Once redirection has been discontinued, it remains discontinued until the drive
is power cycled or until a time equal to the value of IOC Redir Time (300) has
gone by since the last redirectable event.
• Redirection can be turned
off
(disabled) by setting IOC Redir Max (301)
to 0.
• Redirection can be turned
on
(enabled) by setting IOC Redir Time (300)
to 0 and IOC Redir Max (301) to a nonzero value.
Number of rectifier Instantaneous Overcurrent (IOC) events that can occur
before IOC fault redirection is disabled.
See rectifier parameter 300 for a description of the rectifier IOC fault redirect
facility.
This parameter is for use by service personnel only.
This parameter is for use by service personnel only.
Displays the measured temperature of the top rectifier IGBT power module in
degrees C.
301
IOC Redir Max
Range:
0...30
Default:
5
Access:
0
Path:
Communications > In Data Links
See also:
300
302
Service 302
Range:
0...32767
Default:
1000
Access:
0
Path:
Communications > In Data Links
See also:
303
Service 303
Range:
0...32767
Default:
N/A
Access:
0
Path:
Communications > In Data Links
See also:
345
Rct IGBT Tmp Top
Range:
-3276.8...3276.7 °C
Default:
Read Only
Access:
1
Path:
Inputs & Outputs > Temperature etc
See also:
346, 347, 348
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......