Rockwell Automation Publication D2-3518-4 - January 2020
107
Parameter Descriptions
Chapter 9
Specifies the maximum number of times the drive attempts to reset a fault and
restart when the auto restart feature is enabled.
The auto restart feature provides the ability for the drive to automatically
perform a fault reset followed by a start attempt without user or application
intervention. Only certain faults are permitted to be reset. See
more information.
When the auto restart feature is enabled (that is, Auto Rstrt Tries is set to a value
greater than zero), and an auto-resettable fault occurs, the drive stops. After the
number of seconds in Auto Restrt Delay (175) has elapsed, the drive
automatically resets the faulted condition. The drive then issues an internal start
command to start the drive.
If another auto-resettable fault occurs, the cycle repeats up to the number of
attempts specified in Auto Rstrt Tries.
If the drive faults repeatedly for more than the number of attempts specified in
Auto Rstrt Tries with less than 5 minutes between each fault, the drive remains in
the faulted state. The fault Auto Rstrt Tries are logged in the fault queue.
The auto restart feature is disabled when the drive is stopping and during
autotuning. Note that a DC Hold state is considered stopping.
The following conditions abort the reset/run process:
• Issuing a stop command from any control source. (Note that removal of a
2-wire run-fwd or run-rev command is considered a stop command.)
• Issuing a fault reset command from any active source.
• Removing the enable input signal.
• Setting Auto Restrt Tries to zero.
• Occurrence of a fault that is not auto-resettable.
• Removing power from the drive.
• Exhausting an auto-reset/run cycle.
Note that two auto-restart status bits are provided in Drive Status 2 (210): an
active status
bit and a
countdown status
bit.
Sets the time between restart attempts when the auto restart feature is enabled.
See Auto Rstrt Tries (174) for more information about the auto restart feature.
IMPORTANT
The drive re-starts after a fault reset if the start input is still asserted.
175
Auto Rstrt Delay
Range:
0.5...30.0 sec [0.1 sec]
Default:
1.0 sec
Access:
0
Path:
Dynamic Control > Restart Modes
See also:
174
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......