2 INTRODUCTION
Manual ERZ2000-DI · EN1.2 · 2017, December 21st
62
error (e.g. 1200 seconds = 20 minutes). This also applies for the "On-the-fly cali-
bration" function.
The coordinates of the menu in detail:
HC01 Revision Status
Shows the current status of the function
(stationary / running)
HC02 Time stamp 1
Parameter for starting the test process (run-up start)
HC03 Time stamp 2
Parameter for stopping the run-up and starting the ac-
tual test
HC04 Time stamp 3
Parameter for stopping the test and starting the after-
run
HC05 Time stamp 4
Parameter for stopping the after-run and the function
HC06 Revision run
Parameter for a relative specification of the test time,
corresponding to the time between Time stamp 3 and 4
HC07 Pre/post run
Parameter for a relative specification of the run-up and
after-run time, corresponding to the time between Time
stamp 1 and 2 or 3 and 4
HC08 Delay
Parameter for a wait time before the start with Time
stamp 1
There are multiple processes for using the Functional testing function.
Use of the time stamp with manual entry.
If the 4 time stamps are entered, activate the "Start Time1" button. Then the func-
tion starts automatically when the times are reached and stops after the 4th time
stamp has elapsed. The test time, the time for run-up/after-run and the delay are
calculated and adopted from these times.
There is also a very simple option for activating a functional test directly by clicking
on the "Start now" button. For this purpose, the test time and run-up/after-run must
be specified beforehand.
Parameterization of the time stamp with entry by means of remote operation
via the browser.
For this purpose, click on the "
schedule
" button under the table. The 4 time
stamps are calculated from the PC time (not the flow computer time!) and the val-
ues for test time, run-up/after-run and delay. The function starts automatically
when the times are reached and stops after the 4th time stamp has elapsed.
The result of an elapsed function test can be viewed in the browser. For this pur-
pose, click on the "Result of function test" button under the table in the menu
HC
Functional test under running conditions
(
Figure 52: HC Function test menu
)