Appendix
Manual ERZ2000-DI · EN1.2 · 2017, December 21st
116
Appendix
A) Updating software
Caution
A change or update of the software should not be carried out without con-
sulting with the RMG service department!
Please have this change or update carried out by the RMG service depart-
ment.
A change to the software breaks the seal. Please refer to the comments in
chapter 1.5.2 Seal diagram for devices with MID approval.
A.1
Advance information
The main components of the device software are:
x
The
Flow Computer BIOS
.
x
The
application
with a special part, the calibration core.
Each part is identified by:
x
Version number
x
Checksum
x
Time stamp
(date and time of creation)
An SD memory card that is inserted at the bottom left behind the front panel contains
files in the subdirectory \Bin for the Flow Computer BIOS and the application, e.g.:
\Bin\
ERZ2000DI.exe
(application)
\Bin\
F2_008.mot
(Flow Computer BIOS)
When the device is switched off, the SD card can be removed in order to inspect and
edit it on an external PC with a card reader. When switching on the device, the applica-
tion file is read by the SD card and executed under Windows CE (operating system ker-
nel). A new flow computer BIOS must be installed from the SD card to the internal flash
memory with a special procedure. Then the BIOS is active!
A.2
Software identification
There are various options for determining version number, checksum and time stamp of
the software parts: