2. SYSTEM CONFIGURATION
IMSRM02-E6
18
•
CT input cannot be assigned to the TIO
module with voltage/current output.
(Because for voltage or current output, the
heater break alarm function cannot be used.)
•
For the DO-A and DO-B modules,
duplicated alarms cannot be output. For the
DO-A and
DO-B modules, the functions assigned to
each block consisting of four DO module
output points. Channel numbers of the
corresponding TIO module are automatically
set in order from the top for each block of
the functions assigned. For this reason,
duplicate alarms in the same channel and of
the same type cannot be output. However,
the above does not apply to the DO-C
module.
(3) Others
•
The input and output specification of the two channels TIO module are the same for both channels.
[Example]
CT1
CT2
CT3
CT4
CT5
CT6
Ch.A
Ch.B
Ch.C
Ch.D
Ch.E
Ch.F
TIO-B modules
CT module
Ch: Channel
(Assignment example)
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH1
CH2
CH3
CH4
TIO alarm 1
TIO alarm 2
TIO alarm 1
Heater break alarm
DO-A module
Relay contact output
Relay contact output
TC input
TC input
Relay contact output
Current output
TC input
RTD input