When DO modules are mounted together with other function modules
As an example in which the DO modules need to be added for outputting the alarm independently for
each channel, when (DO modules: 3 modules) are added to (TIO-B modules: 7 modules) :
Each consuming output current becomes as follows.
For TIO modules (7 modules): 40 mA
×
7 =
280 mA
,
For DO modules (3 modules): 140 mA
×
3 =
420 mA
280 mA + 420 mA = 700 mA
≤
1000 mA: Maximum power supply capacity
As the total current described above does not exceed the maximum power supply capacity (1000 mA),
up to 10 function modules
can be mounted.