3. DESCRIPTION OF EACH MODULES
IMSRM02-E6
48
z
z
z
z
Open collector output (DO-A type)
The output status is an 8 points/common open collector output.
For the internal circuit driver of the DO module, connect the minus (-) terminal of an external power
supply to the number 6 terminal and connect the positive (+) terminal of the power supply to the
common line of each output.
In using the open collector output, an external power supply of 24 V DC is required.
Note that if this power supply is not connected, there will be no output from the module.
Open Collector Output Wiring Example
External power supply (24 V DC)
Load voltage:
12 to 24 V DC
Maximum load current:
0.1 A/point
0.8 A/common
12 to 24 V DC
Load
Load
-
+
1
2
6
10
COM (+)
COM (-)
DO1
DO8
1
2
3
4
5
6
7
8
9
10
COM
DO1
DO2
DO3
DO4
24 V DC
DO5
DO6
DO7
DO8
+
−−−−