7. FUNCTIONS
IMSRM02-E6
76
(3) Soak time
This is the time period between the time that all the channels reach the temperature set value and the
time of the occurrence of the temperature rise completion.
Temperature set value
or
temperature rise
completion range
Soak time
Temperature rise start
(Simultaneous start
on all channels)
Temperature
rise completion
(1)
(2)
(3)
a
b
c
(1) Channel a has reached the temperature rise completion range.
(2) Channel b has reached the temperature rise completion range.
(3) Channel c has reached the temperature rise completion range.
(4) First order lag digital filter
This is a software filter which reduces input value variations caused by noise. If the time constant of
this filter is set appropriately to match the characteristics of the controlled object and the noise level,
the effects of input noise can be suppressed. However, if the time constant is too small, the filter
may not be effective, while if the time constant is too large, then the input response may actually
deteriorate.
(5) Input programmable range function
This function is used to scale the decimal point position and display range from -1999 to +9999 for
voltage/current input.
[Example]
The display range is set form 0.0 to 100.0 for a voltage input of 1 to 5 V DC
Display
Voltage input
100.0
0
1 V
5 V
Decimal point position
Range
-1999 to +9999
.
-199.9 to +999.9
.
-19.99 to +99.99
.
-1.999 to +9.999