4. MOUNTING
IMSRM02-E6
56
4.4 Mounting the Mother Block
The mother block can be mounted to a panel or DIN rail.
Panel mounting directions
1.
Refer to both the panel mounting dimensions below and the
4.3 Dimensions (P. 54)
when
selecting the location.
4-M3
24
24
77
24
24
77
Double type module
Dimensions for multiple
module mounting.
(Unit: mm)
Single type module
2-M3
77
2.
Remove the module from the mother block. For details of removing the module, see
4.6 Removing the Module
Mainframe (P. 59)
.
3.
Connect the mother blocks together before tightening the screws on the panel.
(Customer must provide the set screws)
M3
×
10
Mother block
Recommended tightening torque:
0.3 N
⋅⋅⋅⋅
m (3 kgf
⋅⋅⋅⋅
cm)
When the mother block is mounted on the panel,
50 mm or more space is required at the top and
bottom of the mother block to attach the module