3.1.2
Checking the condensate siphon
•
Check the condensate siphon. Remove any dirt residues
and refill with clean water to the mark.
3.1.3 Checking the ignition electrode
•
Check the ionisation /ignition electrode for:
- deposits (remove any white deposits with abrasive cloth);
- the adjustment of the ignition electrode (between 3 and 4
mm);
- the quality of the gasket and condition of the porcelain (this
should not be cracked);
•
Check the ionisation current after 1 minute on the display
code
f
l
,
see par
.
2.10.6.
If the read-out value is lower than 3 or higher than 9µA, check
cable and connections are sound if OK
replace the ignition electrode.
The ignition cap is fixed on the ignition electrode and therefore
cannot be removed.