No flue must penetrate
area within dotted lines
round roof light
LTALW7H000020a
Dimensions
Terminal location
Minimum distance
(in mm) to terminal
(room sealed)
A
Directly below an opening, air brick,
opening window, etc.
300
B
Above an opening, air brick, opening window, etc.
300
C
Horizontally to an opening, air brick,
opening window, etc.
300
D
Below a gutter or sanitary pipe work
40
1)
E
Below the eaves
40
F
Below a balcony or carport roof
40
G
Above ground, roof or balcony level
300
H
From vertical drain/soil pipe work
40
1)
J
From an internal or external corner
40
K
From a surface or boundary facing the terminal
600
2)
L
Vertically from a terminal on same wall
1500
M
Horizontally from a terminal on same wall
300
N
From a terminal facing the terminal
1200
P
From an opening in a carport (e.g. door, window) into the building
1200
R
From a vertical structure on the roof
n/a
S
Above an intersection with the roof
n/a
LT.AL.W7H.000.020
table 01 Minimum distances to terminal
1)
= For combustible materials the min should be 150 mm
2)
= Where the terminal is positioned directly opposite an open-
ing in the facing wall the min will be 2 m.
n/a = not applicable.