37
LTALW7H000048b
R
59970LTGBW7H021a
Fan speed [rpm]
H
ii
n
p
u
t
[k
W
]
0
5.0
10.0
15.0
20.0
25.0
30.0
1000
1500
2000
2500
3000
3500
4000
4500
Speed-output ratio
Avanta 18V
2.10.9 Changing the maximum output (Hi) for CH
operation
The maximum output for CH operation can be changed with
parameter
p 17
(maximum fan speed) and is set standard
to the maximum fan speed of 3500 rpm. See the speed-input
ratio figures.
This parameter can be changed from the stand-by status as
follows:
•
P ress the
[enter]
-key
and briefly the
[reset]-
key
until codes
c
and
0
appear alternately in the display.
•
Press the
[+]
-key
until access code
12
is displayed.
•
Press the
[enter]
-key until
p1
appears (codes
p
[
and
[
1
are displayed alternately);
•
Press the
[+]
-key
to go to parameter
17
.
•
Press the
[enter]
-key until
p17
appears (codes
p
[
and
17
are displayed alternately);
•
Press the
[+]
or
[-]-
key to change this value for Avanta
18v,
for example to
35
(3500 rpm corresponds with
18kW).
•
Press
[enter]
-key to confirm the value.
•
Press
[reset]
-key to return to the operating mode.
LT.AL.W7H.000.048
59970LTGBW7H021