38
Remeha Avanta 18v
LTALW7H000052b
R
2.10.10 Restore factory settings
The factory settings can be restored in the service level as fol-
lows:
1. After parameter
p31
has shown, press the
[+]
-key
;
d
f
and
xx
appear alternately;
2. Press
-key;
xx
appears;
3. Read boiler identification plate for value of
d
f
; press
[+]
or
[-]
key to reach this value;
4. Press
-key to confirm;
d
U
and
yy
appear alter-
nately;
5. Read boiler identification plate for value of
d
U
; press
[+]
or
[-]
key to reach this value;
6. Press
-key to confirm; boiler restarts with original factory
settings.
2.11 Putting the boiler out of operation
The boiler must be switched off and allowed to cool down
before any maintenance or repairs are carried out. If the cen-
tral heating system is not going to be used for a long time
(during the holidays, for instance, or frost-free periods) it is
advisable to put the boiler out of operation.
2.11.1 Boiler with frost protection, during longer periods
of non-use
•
Set the room thermostat or other controls to a low tempera-
ture, e.g. 10°C,
•
Switch setting
p4
to
1
(Eco mode), this will switch off
the heat retention function.
Now the boiler will only start working to protect itself against
freezing.
With external frost protection, the boiler can also prevent the
central heating system from freezing.
2.11.2 Boiler without frost protection, during longer
periods of non-use
•
Turn time clock off and allow system to cool down then iso-
late mains power supply at the fused spur unit
•
Isolate the gas supply at the boiler valve
Drain the boiler and central heating system if you will not be
using the home for a long period and there is a chance of
night frost.
LT.AL.W7H.000.052