28
Remeha Avanta 18v
59970LTGBW7H037b
Check
C
59970LTGBW7H015a
•
Open the boiler gas valve and check the static pressure to
the boiler at the measurement point (C) on the gas block.
•
The boiler has been factory tested for natural gas at 20
mbar.
•
The minimum gas inlet pressure is 17 mbar for natural gas
•
The minimum gas inlet pressure is 37 mbar for propane.
•
Check that the gas supply to the boiler is gas tight (in com-
pliance with the current regulations, see
Chapter
7
the maxi-
mum test pressure at the gas pipe inlet, with the boiler gas
valve open, is 60 mbar.
•
Vent the gas pipe by unscrewing the measurement point (C)
on the gas block (tighten it again as soon as the pipe is fully
vented).
•
Check that the gas connections in the boiler are sealed.
•
Check that all electrical connections, including the earth
connection, have been made correctly.
•
Check the electrical connections to the thermostat and other
external controls.
•
Check that the flue-gas and air-supply connections are
sealed.
59970LTGBW7H037
59970LTGBW7H015