2.10.7 Adjust the boiler according to the system
The operating parameters of the Remeha Avanta 18v have
been factory set to suit most systems. However it is possi-
ble to adjust some of the parameters to enable the Remeha
Avanta 18v
to operate more efficiently to match specific system
designs and site conditions. These parameters are split into
two specific sections
1. User level – Parameters
p
1
to
p
6
; can be changed by
the user to suit CH and DHW comfort conditions
2. Service level –
p17
to
dF
; must only be changed by
Broag approved Engineer after consultation with the system
designer.
How to change the parameters at user level can be read on
the “Short reference card” provided and therefore will not be
detailed in this Installation and Service manual.
2.10.8 Changing the parameters at service level (with
access code)
To avoid non authorised adjustments, some parameter settings
can only be changed once the special access code
12
has
been entered. This code may only be used by qualified install-
ers. The following settings can be changed at user and service
level:
Codes in dis-
play
Description
Setting range and notes where applicable
Factory settings
18v
Can
also
be
changed
by
users
p
1
T
set
flow
20 - 85°C
75°C
p
2
T
set
DHW
40 - 65°C
55°C
p
3
Boiler regulation
0 = CH
off
and DHW
off
1 = CH
on
and DHW
on
2 = CH
on
and DHW
off
3 = CH
off
and DHW
on
2
p
4
Eco or comfort setting
0 = comfort setting
1 = eco mode*
2 = regulated by controller
2
p
5
Anticipated current
0 = no anticipated current
for thermostat on/off
1 = anticipated current
for thermostat on/off
0
p
6
Display off automati-
cally
0 = display stays off
1 = display stays on
2 = display light switches off automatically after 3 minutes
2