2.10 Commissioning
2.10.1 Control Panel
The control panel of the Remeha Avanta 18v has 4 function
keys and a LED display. The function keys are used to read or
change the settings and temperatures.
1 = display
2 =
[reset]
key
3 =
[-]
key
4 =
[+]
key
5 =
[enter]
key
The display has two positions and displays information on the
current operating status of the boiler and any errors. Numbers,
dots and/or letters can appear in the display.
If no key is pressed for longer than three minutes with the
“boiler in stand-by mode”, only one dot is lit. With the “boiler
operating”, two dots are displayed.
•
Press any key and the current boiler status and operation
code will appear in the display.
•
In the event of a fault, the fault code is displayed instead of
the dots.
2.10.2 Additional guidelines for commissioning
•
When commissioning, complete the Boiler Log Book.
•
Work through all the stages of this section, complete the
commissioning details in the supplied boiler log book
and send a copy of the completed documents to Broag to
register the boiler.
•
This Avanta boiler has been live test fired on the production
line and set up for Natural Gas with an inlet gas pressure
of 17- 20 mbar whilst operating and should therefore not
require any further adjustments.
The boiler must not be put into operation with a different type
of gas without reference to Broag.
2.10.3 Putting the boiler into operation
This section details the procedure for putting the boiler into
operation. There are 7 stages to the procedure:
1.
Isolating the power supply and opening the front cover;
2.
Checking the connections and making the boiler operational;
3.
Switching the boiler on and setting the controls;
4.
Checking/setting the gas/air ratio at full load;
5.
Checking/setting the gas/air ratio at low load;
6.
Making the boiler ready for use;
7.
Instructing the user.