6. Re-Assembling the boiler and checking the combustion
•
Re-assemble all the components in reverse order.
•
Remember to connect the fan plug again before it is
completely home on the front of the heat exchanger.
•
Check that the packing between the front plate and the heat
exchanger has been fitted correctly.
•
Switch the boiler back on.
•
Check the CO
2
/O
2
-percentage,
2.10.3, point 4.
•
Check the ionisation current by reading the display,
see
par.3.1.3
•
Check the connections on the gas block on gas-leaking.
Fill in the Boiler Log Book after conducting any maintenance.