3 INSPECTION AND MAINTENANCE
The Remeha Avanta 18v is practically maintenance free but
should be inspected annually.
If during the annual inspection the flue gas analysis indicates
that the values are outside the figures given
in table 09
,
maintenance work should be carried out as described in
par.3.2.
Also carry out maintenance if the ionisation read-out
value is lower than 3 or higher than 9µA, or when the flame
core is not satisfying.
Only Remeha spare parts/materials should be used.
All service and maintenance must be carried out by a quali-
fied Engineer with the relevant training and certification (i.e.
CORGI - ACS - IEE registrations etc).
3.1 Inspection
The annual inspection of the Remeha Avanta 18v can be lim-
ited to the following checks:
- check the flue pipes and air supply pipes for leaks, see par.
3.1.1.;
- check and clean (if necessary) the condensate siphon, see
par.3.1.2.;
- check the ignition electrode and ionisation, see par. 3.1.3;
- check the combustion and flame colour, see par. 3.1.4;
- fill in the boiler log book.
3.1.1 Checking the flue pipes and air supply pipes for
leaks
•
Check that the flue and air-supply connections and pipes
are sealed and the terminal exit is clear.