15
2 - MENU OPTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
i - Component test
This can be done only when the boiler is off and allows you to select the components to be tested:
•
Spark plug:
runs for a test time during which the panel shows the countdown timer in seconds.
•
Auger:
this is fed for a test time during which the panel shows the countdown time in seconds.
•
Aspirator:
this is run at 2500 rpm
for a test time during which the panel shows the countdown time in seconds.
•
Pump:
this is run for a test time during which the panel shows the countdown time in seconds.
•
3 way:
the 3-way valve is run for a test time during which the panel shows the countdown time in seconds.
NOTE:
The technician can stop the test time whenever by quickly pressing the ON/OFF key.
Enable the "Component test" function (only with boiler off) as follows:
•
Press key 3 ''menu''.
•
Use the arrow keys to scroll through and select "Settings"
•
Press 3 “menu” to confirm.
•
Use the arrow keys to scroll through and select ''Component test''
•
Press 3 “menu” to confirm.
•
Use the + - keys to select the test to be carried out.
Press "menu" to confirm and "esc" to exit
j - Lambda Test (can only be activated when the stove is off)
This function only be activated when the boiler is off. When activated, the fan runs at maximum and the Lambda probe is powered. This
state lasts for 60" and the countdown is shown on the panel.
NOTE:
The technician can stop this phase at any moment by quickly pressing the on/off key.
The percentage of oxygen detected by the lambda probe is shown on the display.
k - Chimney sweeper function (for maintenance workers only)
This function can only be activated when the boiler is off and power is supplied, and it forces operation of the boiler at the parameters
required by the standards.
Attention:
During this state (20 minutes, when the countdown is shown on the panel) the actions of the ambient thermostat/puffer/
ambient set point/ H
2
0 set point have no effect.
All the safety devices remain active. The boiler turns off automatically when the water temperature reaches 85°C.
The technician can stop this pressing the phase at any moment by quickly
Enable the "Chimney sweeper" function as follows:
•
Press the ''menu'' key.
•
Use the arrow keys to scroll through and select "Settings"
•
Press “menu” to confirm.
•
Use the arrow keys to scroll through and select ''Chimney sweeper function''
•
Press “menu” to confirm.
•
Use the + - keys to select "On" (Off by default)
•
Press ''menu'' to confirm and ''esc'' to exit.