Chapter 8: Using the Command Line Interface
302
Setting the Sensor's Upper Warning Threshold
This command syntax configures the Upper Warning threshold of a
numeric environmental sensor.
config:#
sensor externalsensor <n> <sensor type> upperWarning <option>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PXE web interface or
using the show command in the CLI. It is an integer between 1 and
32.
<sensor type> is one of these sensor types:
temperature,
humidity,
airPressure or air Flow
.
Note: If the specified sensor type does not match the type of the
specified environmental sensor, this error message appears:
"Specified sensor type 'XXX' does not match the sensor's type
(<sensortype>)," where XXX is the specified sensor type, and
<sensortype> is the correct sensor type.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the upper warning threshold for the
specified environmental sensor.
disable
Disables the upper warning threshold for the
specified environmental sensor.
A numeric
value
Sets a value for the upper warning threshold of
the specified environmental sensor and enables
this threshold at the same time.
Setting the Sensor's Lower Critical Threshold
This command syntax configures the Lower Critical threshold of a
numeric environmental sensor.