Chapter 6: Using the Web Interface
118
Tip: You can reset all active energy readings at at time. See
Resetting
All Active Energy Readings
(on page 77).
Disabling an Inlet (for Multi-Inlet PDUs)
The PXE, if it has more than one inlet, enables all inlets by default so
that the PXE detects and displays all sensors' readings and states, and
reports or shows warnings, events or alarm notifications associated with
all inlets, outlets and overcurrent protectors (if available).
After disabling an inlet, the following information or feature is no longer
available:
All of the sensor readings, states, warnings, event or alarm
notifications associated with the disabled inlet
All of the sensor readings, states, warnings, event or alarm
notifications for the outlets and overcurrent protectors associated
with the disabled inlet
The outlet-switching functionality, if available, for those outlets
associated with the disabled inlet
Exception: All active energy sensors continue to accumulate data
regardless of whether any inlet has been disabled.
Warning: A disabled inlet, if remaining connected to a power source,
continues to receive power from the connected power source and
supplies power continuously to the associated outlets and overcurrent
protectors.
To disable an inlet:
1. Click the Inlets folder in the PX Explorer pane, and the Inlets page
opens in the right pane.
2. Select the inlet that you want to disable.
3. Click
Setup.
4. Select the "Disable this inlet" checkbox.
5. To disable additional inlets, repeat the above steps.