normally closed master valve, the typical installation should have no flow and the limit
should be set to zero. For systems which have a normally open master valve and the
possibility of supplemental watering due to quick coupler manual devices, you have
the option of setting a non-zero value which shall be allowed when the controller does
not have any active stations. If this value is exceeded the unscheduled flow fault occurs.
Note: This SETUP function will be skipped if you have not enabled the flow features.
EXAMPLE: You wish to select an Unscheduled Flow limit of 25 GPM.
Successively Press:
until you see
Press:
you will see
Press:
FLOW CHECK DELAY
This feature allows you to program a delay after any change of stations for which no flow
limits will be checked.
Whenever there is any change in which stations are on (any station gets turned on or off),
the controller will not check for any flow limits from the time of the change until this
delay has expired; this gives the system time to stabilize before any flow limit checking
takes place.
The flow check delay can be set , from 1 to 6 minutes, in 1 minute increments.
Note: This SETUP function will be skipped if you have not enabled the flow features.
EXAMPLE: You wish to set the flow check delay to 4 minutes.
Successively Press:
until you see
Press:
you will see
Press:
TOTALIZER
This feature allows you to view and clear the total gallons used. (The Totalizer value can
also be viewed by using the REVIEW mode.)
SETUP
U N S C H 2 0 0
PROGRAM
U N S C H 0 2 5
PROGRAM
QUIT
THU
5
MON
2
ENTER
55
F D E L A Y 2
PROGRAM
SETUP
QUIT
F D E L A Y 4
PROGRAM
ENTER