[ Table 9-3 : System General Events Protection List ]
Problem Confirmation
I
100
9.1.3 System General Events (Protection)
It is an unregistered fault. Turn off and restart
the system. Please contact the Q CELLS
Service –Hotline, if an error occurs
continuously.
Unregistered Failure
Unknown
P01P
WEB Display
HMI Display
Description
Measures
Please turn off and restart the system.
If an error occurs repeatedly, it is necessary
to replace the Control Board.
ADC Measure Error
Protection
ADC P
P11P
Please turn off and restart the system. If an
error occurs repeatedly, it is necessary to
replace the Control Board.
DSP Master FRAM
Communication Error
Protection
DSPM FRAM
P
P21P
Please turn off and restart the system.
If an error occurs repeatedly, it is necessary
to replace the Control Board.
DSP Slave FRAM
Communication Error
Protection
DSPS FRAM P
P22P
It is an unregistered fault. Turn off and restart
the system. Please contact the Q CELLS
Service –Hotline, if an error occurs
continuously.
DSPM-DSPS
Communication Error
Protection
DSP COM P
P23P
Please check emergency switch.
DSP-Emergency Trip
Protection
DSP-EMG
TRIP P
P03P
Please update DSP Master software again.
DSP Master Remote
Update Fail Protection
DSPM
UPDATE P
P12P
Please update DSP Slave software again.
DSP Slave Remote
Update Fail Protection
DSPS
UPDATE P
P13P
Please update PMS software again.
PMS Remote Update
Fail Protection
PMS
UPDATE P
P14P
DSP and PMS versions are different.
Please re-install the DSP software.
DSP Firmware Version
Error Protection
DSP VER P
P15P
Please update DSP Slave software again.
PMS Firmware Version
Error Protection
PMS VER P
P16P
Type : PROTECTION