![background image](http://html.mh-extra.com/html/q-cells/q-home-ess-hyb-g2/q-home-ess-hyb-g2_installation-manual_764141115.webp)
[ Figure 11-1 : Derating Curve ]
Technical Specifications
I
108
Ambient temperature (°C)
20
0
0.5
1.5
2.5
3.5
1
2
3
4
4.5
5
30
40
50
60
70
Output Power (kW)
[ Figure 11-2 : Battery Charge Limit ]
[ Table 11-3 : Maximum Charge Current Limit ]
Cell Body Temperature (°C)
Max Charge Current
Australia & New Zealand
0
T<0°C
0
2
4
6
8
10
Current (A)
0°C ≤ T < 10°C 10°C ≤ T < 25°C 25°C ≤ T < 40°C 40°C ≤ T < 50°C
T ≥ 50°C
3.5
7
9.8
3.5
2.1
Item
Specification
Maximum
Charge Current(*)
(*) : Maximum Charge Current
- If the battery is discharged at the maximum discharge current / power, the battery should be cooled
its ambient temperature before discharging again.
Cell body / module temperature
9.8A
3.5A
2.1A
7A
3.5A
0A
25°C ≤ T < 40°C
40°C ≤ T < 50°C
T ≥ 50°C
10°C ≤ T < 25°C
0°C ≤ T < 10°C
T < 0°C
Remarks
Germany