![background image](http://html.mh-extra.com/html/q-cells/q-home-ess-hyb-g2/q-home-ess-hyb-g2_installation-manual_764141032.webp)
NOTICE
The Q.HOME+ ESS HYB G2 system can be damaged by static discharge.
Before you touch a component inside the Q.HOME+ ESS HYB G2, ground yourself
by touching PE or a grounded object.
5. Electrical Connections
25
I
Electrical Connections
CAUTION
When handling with the Li-Ion Battery for the Q.HOME+ ESS HYB G2, you must
wear the following personal protective equipment : High voltage rated rubber gloves
Safety goggles or other protective eye equipment 40-minute standby period of time
to complete discharging in the system before testing electrical parts inside the system!
Follow the guidelines below when handling the Li-Ion Battery.
Do not intentionally short circuit the positive (+) and negative (-) terminals with a metallic
object.
Do not remove the cap on the terminals. If the cap is removed, avoid contact between the
metals and the Battery terminals. Do not damage the screw thread.
Do not use seriously scarred or deformed Battery. Dispose immediately according to
proper regulations.
Do not damage sheath of cable and connectors.
[ Figure 4-10 : Stand assembly Step 1~7 ]
• Step 7 : Assemble the battery in the same way.
• Step 6 : After assembling INVERTER A’SSY and
stand, tighten SCREW.
STEP 6
STEP 7
*
Use the Wall Mount Screw
to disassemble it.
M
8
x4
5
,
Washer
(2 point)