3.
Strip the cable ends, fit the cable ends with cable end
sleeves (⌀ max = 0.5 mm
2
) and connect the cable ends to the
2-wire connector: 1 = plus, 2 = minus
4.
Insert approx. 5 cm of the measuring line into the sensor
5.
Tighten the clamping screw on the threaded connector
6.
Push the top part of the sensor right into the sensor shaft and
tighten it clockwise up to the stop
Screw the measuring line coming from the controller onto the
respective sensor.
7.3 Adjusting the Flow Sensor Switching Point
Task:
The flow sensor should switch when the flow falls;
the flow sensor is connected as an N/C (Term. 1 -
Term. 2 = NC - C):
1.
Use the ball valve to adjust the flow to 50 l/h
2.
Hold the flow sensor in place and loosen the mounting clip a
little
3.
Press the float down to 40 l/h using the flow sensor,
ð
The connected alarm device should switch off
4.
Hold the flow sensor in this position and tighten the mounting
clip
5.
Lower the flow for test purposes
ð
The alarm device should switch off
6.
Check the threaded connector for leak-tightness
A0102
Fig. 7: 2-wire connection