HP-MSM-HB
35,0(6
8.1.2
Water pressure
For a reliable operation a water flow rate of
• 7 l/min to 8 l/min (at 10 kW)
• 14 l/min to 16 l/min (at 20 kW)
is required. Normally, 2 bar primary pressure at the entrance of the absorber are sufficient in case of an un-
pressurized outflow.
NOTICE
Damage/Destruction of the device due to overpressure
X
The maximum permissible water inlet pressure must not exceed 4 bar.
8.1.3
Humidity
• The device must not be operated in a condensing atmosphere. The humidity has to be considered in
order to prevent condensates within and outside the device.
• The temperature of the cooling water must not be lower than the dew point (see Tab. 8.1 on page 29).
NOTICE
Damage/Destruction of the device due to condensing water
Condensation water inside of the objective will lead to damage.
X
Mind the dew-point in Tab. 8.1 on page 29.
Do only cool the device during the measuring operation. We recommend starting the cooling approx. 2 min-
utes before the measurement and terminating it approx. 1 minute after the measurement.
Cooling water temperatur
e in °C
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Air temperature in °C
100
50
60
70
80
40
30
20
10
Relative humidity in %
Tab. 8.1:
Dew point diagram:
The temperature of the cooling water must not be lower than the dew point
Example
Air temperature:
22 °C
Relative humidity:
60 %
The cooling water temperature cannot fall below 14 °C.