Powtran PI8600 F Series User Manual Download Page 89

Section  V  Parameter  Function  Table 

87 

 

S

ect
io

n

 V

 

15 

Arrival of FDT set frequency2  Arrive at frequency 2 FDT set 

16 

Inspection Level Of FDT 
Frequency   

FDT frequency levels to meet the inspection 
conditions,o29~ o31 

17 

Arrival of preset counting 
value 

Present counting value arrives at preset counting 
value 

18 

Arrival of counting value 
upper limitation   

Present counting value arrives at upper 
limitation of counting value. 

19 

Program ruuning one period 
completion 

Program runs one period to complete. 

20 

Inspection in speed trick mode 

Inverter is under speed trick state, the valid time 
is A11 

21 

No command running state 

Inverter is under N command running state 

22 

REW command of inverter   

Inverter is under reverse running command   

23 

Deceleration running 

Inverter is under deceleration running 

24 

Acceleration running   
celerate running 

Inverter is under acceleration running   

25 

Arrival of high pressure 

Arrival at hight pressure 

26 

Arrival of low pressure 

Arrival at low pressure 

27 

Arrival of inverter rate current  Arrival at inverter rate current 

28 

Arrival of motor rate current 

Arrival at motor rate current 

29 

Arrival of input frequency 
lower limitation 

Present  set  frequency  is  less  than  frequency 
lower limitation 

30 

Arrival of current upper 
limitation 

Arrive at current of upper limitation 

31 

Arrival of current lower 
limitation 

Arrive at current of lower limitation 

32 

Time to reach limit time 1   

Timing action mode refer to o65 configuration 

33 

Time to reach limit time 2 

Timing action mode refer to o66 configuration 

34 

Inverter ready to run 

The  end  of  initialization  when  the  drive  power 
on , running command is acceptable. 

  

o25 

Output signal delay 1 

0~32.000 

o26 

Output signal delay 2 

0~32.000 

o27 

Output signal delay 3 

0~32.000 

o28 

Output signal delay 4

8000 

o25~o28 defines o21~o24 output signal reaction delay time, unit is S. 

Output signal cut off action without delay. 

o29 

FDT set frequency 1

 

o30~

Max frequency

 

Hz 

0.00 

o30 

FDT set frequency 2

 

0~o29 

Hz 

0.00 

o31 

FDT inspection range

   

0.00~5.00 

Hz 

0.00 

Frequency detection range as 0

  the output signal terminal movement is as below 

 

Summary of Contents for PI8600 F Series

Page 1: ...peed sensorless vector control This product adopts the advanced sensorless vector control technology combined with the application of inverter technology in China features to achieve high performance...

Page 2: ...0137 69 5 2 5 IO Function System o00 o68 0x0200 0x0244 81 5 2 6 Multi speed PLC Group H00 H55 0x0300 0x0337 101 5 2 7 V Fcurve Group U00 U15 0x0400 0x040F 110 5 2 8 PID Parameter P00 P12 0x0500 0x050C...

Page 3: ...00 400 0Hz 1 220V 50 60Hz POWTRAN TECHNOLOGY CO LTD PI8600A1 R75G1 AC Motor Drivers Model Serial No Bar Code Output Spec Input Spec 1 1 2 Model description 2 type code A normal elided B inhanced D si...

Page 4: ...of the frequency inverter must be grounded to the earthing connections correctly and securely according to the national electrical safety specifications and other applicable standards Please don t shu...

Page 5: ...lid exists 2 2 Installation The frequency inverter must be installed by wall hooking in the indoor room with adequate ventilation with enough space left between it and the adjacent objects or damper w...

Page 6: ...Section II Installtion Standby Circuit 4 Section II 2 3 1 PI8600 Diagram ALARM V A Hz FWD REV s PRG FWD MF1 ESC STOP RESET SET C ALARM FWD R232 R485 PICOM RS485 RS232...

Page 7: ...rminal Description Functions Input signal DI1 DI1 input terminal Multi functions input terminal For details Please read o36 o46 Enter a valid polarity can be controlled by o47 DI1 DI4 Drive model can...

Page 8: ...o02 o03 can set input voltage current arrange o08 o09 Set the input signal corresponding to set value DA1 Multifunction Analog output signal 1 JP1 1 2 0 20mA JP1 2 3 0 10VDC o15 set analog output ana...

Page 9: ...the distance between the frequency inverter and motor must not be greater than 50 meters maximum When it is above 4kHz this distance should be reduced The cable for this connection had better be laid...

Page 10: ...ction A43 A44 1 MF defined as minus function A43 A44 2 MF defined as free stop function A43 A44 3 MF defined as forward function A43 A44 4 MF defined as reverse function A43 A44 5 MF defined as Punctu...

Page 11: ...fault confirmation Forward running key drive forward running ENTER have the same function with PRG refer to explaination of key PRG Invalid in the monitoring state Monitor Select 1 Numerical Display d...

Page 12: ...us 4 Through potentiometerSwitch to F01Fre Set by K 5 Press PRG or ENTER enter into F01 Fre Set by K parameter modify status 6 Through PRG or ENTER adjust the value is modified bit 7 Through potentiom...

Page 13: ...yboard 1 Under monitoring status press PRG into parameter group to check status 2 Through potentiometerSwitch to y00 23 System FG 3 Press ENTER enter into y00 23 System FG parameter group to check sta...

Page 14: ...1 to reset system parameter 1 Under monitoring status press PRG into parameter group to query status 2 Through potentiometerSwitch to y00 23 System FG 3 Press PRG enter into y00 23 System FG parameter...

Page 15: ...status 4 Through potentiometerSwitch to y01 Upload To Keyboard 5 Press PRG enter into y01 Upload To Keyboard parameter modify status 6 Through potentiometer adjust to 5 7 Finish the adjustment press...

Page 16: ...range A45 A46 A48 keyboard potentiometer setting X1 correspond to Y1 Keyboard potentiometer setting the starting point for the corresponding value Setting range 100 100 A49 keyboard potentiometer sett...

Page 17: ...tting range 0 100 o08 AI2 input X1 correspond to Y1 Keyboard potentiometer setting the starting point for the corresponding value Setting range 100 100 o09 AI2 input X2 correspond to Y2 Keyboard poten...

Page 18: ...to the motor power reset the factory value of y00 5 Select motor parameters motor parameters set in accordance with motor nameplate set of parameters rated power rated current rated voltage the number...

Page 19: ...nd test running finish Upper torque setting C13 C14 Set PG pulses C28 PG directions C30 running Observe motor speed S06 Observe the motor current excitation component torque fluctuation component Stop...

Page 20: ...H Multi speed PLC group Multi speed running PLCrunning 03 101 U V F parameter group User defined V Fcurve 04 110 P PID function group Internal PID parameter setting 05 111 E Extend function froup Cons...

Page 21: ...set excitation heft percentage N 54 S13 Excitation heft actual value Motor actual excitation heft percentage N 54 S14 Torque heft Set value Motor set torque percentage N 54 S15 Torque heft actual valu...

Page 22: ...setting 5 Digital Pulse Set 6 PID regulation mode 7 F04 The relationship between main and auxiliary setting frequency The main setting individual control 0 0 Y 57 The auxiliary setting individual con...

Page 23: ...110 100 Y 60 F12 Maximum frequency 10 00 320 00 50 00 N 60 F13 Lower frequency 0 00 Upper frequency 0 00 N 61 F14 Upper frequency Lower frequency Upper frequency 50 00 N 61 F15 Basic frequency 5 00 M...

Page 24: ...p when the DC braking current 0 135 100 Y 64 F29 Stop and braking wait time 0 0 60 0 0 0 Y 64 F30 Brake time stop 0 0 60 0 0 0 Y 64 F31 Stop and brake starting frequency 0 00 Max frequency 0 00 Y 64 F...

Page 25: ...et frequency working time 0 0 60 0 0 0 Y 67 F45 Motor running direction 1 bit Direction command forward command FWD let motor forward running 0 0000 N 67 Direction command forward command FWD let moto...

Page 26: ...min 1 Acceleration time h 2 Acceleration time day 3 1000bit Deceleration time s 0 Deceleration time min 1 Deceleration time h 2 Deceleration time day 3 F49 Running configuration word 1 bit Running dir...

Page 27: ...ard DC bus voltage 70 Y 72 A10 Power down tracking options N 0 0 Y 72 Power off tracking mode 1 Startup tracking mode 2 A11 Power down tracking time 0 0 20 0 0 0 Y 73 A12 Power down frequency drop poi...

Page 28: ...Y 75 A26 Fault reset time 0 5 20 0 1 0 Y 75 A27 Fan startup temperature 0 0 60 0 0 0 Y 75 A28 This inverter communication address 1 128 8 Y 76 A29 Baud rate Baud rate is 1200 0 4 Y 76 Baud rate is 240...

Page 29: ...0 0FF 0FF Y 77 A38 UP DN control 1 bit Power down to save 0 0000 Y 78 Power down to clear saving 1 10 bit Saving after stopping 0 Stop command to clear saving 1 Cleared at the end of stopping 2 100 b...

Page 30: ...5 A40 UP DN adjustment value 300 00 300 00 0 00 N 80 A41 UP adjustment ratio 0 01 20 00 0 01 Y 80 A42 DN adjustment ratio 0 01 20 00 0 01 Y 80 A43 A44 The definition of multifunction keys MF1 and MF2...

Page 31: ...82 A50 Keyboad potentiometer control 1bit Saving after power down 0 0000 Y 82 Cleared after power down 1 10bit Saving after stoppoing 0 Clear saving after stopping command 1 Clear saving at end of st...

Page 32: ...t X2 corresponding value Y28000 83 o08 AI2 input X1 corresponding Value Y1 100 0 100 0 0 0 Y 83 o09 AI2 input X2 corresponding value Y2 100 0 100 0 100 0 Y 84 o10 AI3 input X1 corresponding value Y180...

Page 33: ...O4output signal select 48000 No function 0 0 0 1 8 Y Y Y Y 86 Fault warning 1 Over current inspection 2 Over load inspection 3 Over voltage inspection 4 Less voltage inspection 5 Low load inspection 6...

Page 34: ...er limitation 30 Arrival of current lower limitation 31 Time to reach limit time 1 32 Time to reach limit time 2 33 Inverter ready to run operation 34 o25 Output signal delay 1 0 32 000 0 Y 89 o26 Out...

Page 35: ...minalfunction selection 8000 DI6 inputterminalfunction selection 8000 DI7 inputterminalfunction selection8000 DI8 inputterminalfunction selection8000 AI1 inputterminal functionselection8000 AI2 inputt...

Page 36: ...unning control mode switch 3 25 FWD torque upper limit switch 1 26 FWD torque upper limit switch 2 27 FWD torque upper limit switch 3 28 REV torque upper limit switch 1 29 REV torque upper limit switc...

Page 37: ...ue loading 49 Out fault signal input level 50 1 pump start 51 1 pump stop 52 2 pump start 53 2 pump stop 54 3 pump start 55 3 pump stop 56 4 pump start 57 4 pump stop 58 Manual rotate command 59 Time...

Page 38: ...bit Reload after power on 0 Be cleared after powter on 1 Keep count after power on 2 1000bit Counting period 0 Output signal valid time 20ms 1 Output signal valid time 100ms 2 Output signal valid tim...

Page 39: ...t Time 1 0 0 3200 0 2 0 Y 103 o68 Limit Time 2 0 0 3200 0 2 0 Y 103 5 1 6 Multi speed PLC Group H00 H55 0x0300 0x0337 Code Description LCD Setting Range Factory Setting Change Limited Reference page H...

Page 40: ...1 1000 bit Running at the speed when start up segment 0 Running at the speed before the machine stopped 1 H03 1 Segment speed setting 1X Lower frequency upper frequency 3 00 Y 106 H04 2 Segment speed...

Page 41: ...ent running time T3 0 0 3200 0 2 0 Y 108 H22 4 Segment running time T4 0 0 3200 0 2 0 Y 108 H23 5 Segment running time T5 0 0 3200 0 2 0 Y 108 H24 6 Segment running time T6 0 0 3200 0 2 0 Y 108 H25 7...

Page 42: ...ites 1 Running time hours 2 Running time days 3 100 bit Acceleration time seconds 0 Acceleration time munites 1 Acceleration time hours 2 Acceleration time days 3 1000bit Deceleration time seconds 0 D...

Page 43: ...V F setting voltage 4 U05 U09 40 N 112 U08 V F setting frequency5 U06 U10 25 00 N 112 U09 V F setting voltage 5 U07 U11 50 N 112 U10 V F setting frequency6 U08 U12 30 00 N 112 U11 V F setting voltage...

Page 44: ...rnal analogy giving 2 AI3 external analogy giving8000 3 Keyboard potentiometer giving 4 Multi step digital voltage giving 5 Digital pulse set 6 P04 Keyboard set signal 0 0 100 0 50 0 Y 114 P05 PID int...

Page 45: ...ation power 13 Current regulation power 14 Extruding machine 15 E01 Starting pressure deviation 0 0 100 0 10 0 Y 115 E02 Starting delay time 0 0 3200 0 5 0 Y 115 E03 Stop frequency 0 50 00 5 00 N 115...

Page 46: ...0000 Y 118 Variable frequency pump stop 1 Free stop 2 Water supply pump stop 3 10 bit all pumps status when fault occur Keep current situation 0 All pumps stop 1 100 bit Altern ation shift mode Variab...

Page 47: ...bit Pump 2 stop 0 Pump 2 run invariable frequency 1 Pump 2 run inworking frequency 2 100bit Pump 3 stop 0 Pump 3 run invariable frequency 1 Pump 3 run in working frequency 2 1000bit Pump 4 stop 0 Pump...

Page 48: ...1 C01 Speed loop low speed Ti 0 01 100 00 0 25 Y 122 C02 Speed loop low speed Td 0 000 1 000 0 000 Y 122 C03 Speed loop low speed P 0 150 100 Y 122 C04 Speed loop low speed shift frequency 0 0 C08 7 0...

Page 49: ...ting mode 1 bit Setting mode Set by keyboard or RS485 0 0000 Y 123 AI1 external analogy8000 1 AI2 external analogy giving 2 AI3 external analogy giving8000 3 Keypad potentiometer giving 4 Multi step d...

Page 50: ...eration time 0 0 200 0 1 0 Y 123 C23 Low speed excitation compensation 0 100 30 Y 123 C24 Current loop Ti 0 9999 500 Y 123 C25 Current loop P 0 1000 100 Y 123 C26 PG electronic gear A 1 5000 1 Y 123 C...

Page 51: ...inductance 0 0 3200 0 Y 127 b09 Motor 1 mutual inductance 0 0 3200 0 Y 127 b10 Motor selection Motor 1 0 0 N 127 Motor 2 1 b11 Motor parameter measurement No measurement 0 0 N 127 Calculate by label...

Page 52: ...y01 Parameter upload to keyboard No action 0 0 N 129 Reset system parameter with keyboard memory area1 1 Reset system parameter with keyboard memory area2 2 Reset system parameter withb keyboard memor...

Page 53: ...5 2 Functional parameter specification 5 2 1 Menu Group Code Description LCD Function Discription Group ID Reference page S Monitor function group Monitor frequency current and other 16 monitor objec...

Page 54: ...50 00Hz Gain Speed surveillance A35 100 0 the pole of the motor b03 b16 2 the real speed of the motor 1500rpm When stop based Residual voltage test motor speed renew speed 500ms The real speed 60 resi...

Page 55: ...verter driving a motor occasions suitable for a inverter driving multiple motors occasions suitable for the inverter as a variable frequency power supplies 1 Sensorless vector control High performance...

Page 56: ...ent digital voltage setting o36 o46 IO input terminal function set to 11 12 13 switch H47 H54 Multi digital voltage setting 100 Corresponding to the maximum frequency 6 Digital pulse setting Digital p...

Page 57: ...minal and DI8 terminal reseting After use digital pulse input o43set to 0 Otherwise the function settings will take effect can check the pulse input status o58 be limited to low speed pulse 7 PID regu...

Page 58: ...n auxiliary setting frequency main auxiliary setting frequency f f f The relationship between main give and auxiliary given Main Auxiliary f f f t f f f f f max f t max f auxiliary main setting freque...

Page 59: ...the keyboard terminal Rs485 the slave unit will not run the proportion liknge host unit s command it needs once again to respond to host commands through the keyboard terminal RS485 or the proportion...

Page 60: ...e torque curve torque boost Cut off frequency Constant torque curve torque boost motor rated voltage Enhance voltage Basic frequency Voltage Cut off frequency Frequency Frequency Torque increase is ma...

Page 61: ...frequency Start the motor that in the status of stopping the inverter outputs accelerate starting from 0Hz accordance with the step 1 acceleration time towards the upper or the setting frequency to a...

Page 62: ...ric disturbance Switch dissipation is expressed as following Carrier frequency Motor noise Electric disturbance Switch dissipation 1 0KHz Big Small Small Big Small Big 8 0KHz 16 0KHz The relationship...

Page 63: ...t the slope of the output frequency at constant segment 3 Indicate that the slope of the output frequency is reduced to 0 from the max Such as setting the S curve acceleration and deceleration acceler...

Page 64: ...ncy set frequency Minimum frequency lower limit frequency lower limit frequency lower limit frequency actual frequency set frequency Minimum frequency lower frequency Minimum frequency Minimum frequen...

Page 65: ...orque and can not exceed the motor rated current braking frequency time time Stop braking RUN STOP STOP OFF stop braking time RUN ON setting frequency output frequency stop brake wait time setting fre...

Page 66: ...time before jog 0 Jog end and acceleration deceleration time save the set acceleration and deceleration time before jog 1 F36 Jog frequency setting Lower frequency upper frequency Hz 6 00 Y Jog accel...

Page 67: ...y area F43 Preset frequency 0 00 Max frequency Hz 0 00 Y F44 Preset frequency working time 0 0 60 0 s 0 0 Y After inverter startup it firstly run with preset frequency running time is preset frequency...

Page 68: ...parameter to achieve the motor forward to reverse or from reverse running to forward the waiting time of motor speed being zero F47 output frequency running time F47 Frequency multiple setting 1 0 0 N...

Page 69: ...4 Adjustment of keyboard potentiometer giving Actual acc time Acc time keyboard potentiometer giving percentage 5 Adjustment of multi steps digital voltage giving Actual acc time Acc time multi steps...

Page 70: ...05 0 1 2 control direction of 0 step speed When running control mode F05 3 Setting the value and terminal FWD REV jointly decide the direction of 0 step speed FWD priority FWD 1runningdirection REV 1r...

Page 71: ...0B00 0B01 0B02 Y Y Y X1000 X100 X10 bit 00 0B 0 63 0x00 0x3F Code Keyboard display Parameter group N Function spec Parameter N 16 hexadecimal input S Monitor function group 0B S 0 16 0x00 0x10 F Basi...

Page 72: ...fluctuate the output voltage fluctuation is very small the V F curve characteristic has always been close to setting state of rated input voltage 0 Function invalid 1 Function Valid 2 Function Valid...

Page 73: ...tracking from 0 Hz 1 Power down tracking When the inverter instantaneous power off and re start the motor will continue running with current speed and direction If the power off time is longer than A...

Page 74: ...drop speed In operation process when the motor current surpass value A16 set motor will decelerate according to deceleration time A15 set until current below value A16 set In operation process when th...

Page 75: ...n Series Electronic Thermal Protection Level Parameters F 120 A24 G 150 A24 A24 set the electronic thermal protection level When the current is the rated motor current multiples the parameter the driv...

Page 76: ...ation The proportion of linkage function The proportion of linkage host inverter This inverter communication address 128 Communication interface A is set as host inverter communication interface for p...

Page 77: ...inverter running accumulating or not 0 Auto clear to 0 after power on 1 Continue to accumulate running time after power on A34 Unit of total running time hour 0 0 Y Day 1 The set for unit of accumulat...

Page 78: ...FWD key 1 0 Unlock STOP key 1 Lock STOP key 2 0 Unlock PRG key 1 Lock PRG key 3 0 unlock SET key 1 Lock SET key 4 0 Unlock ESC key 1 Lock ESC key 5 0 Unlock MF1 key 1 Lock MF1 key 6 0 Unlock MF2 key...

Page 79: ...P DN control validity of adjustment 0 UP DN invalid adjustment 1 UP DN valid adjustment A39 UP DN time 1 bit UP fix speed 0 0000 N UP fix times 1 10 bit DN fix speed 0 DN fix times 1 100 bit UP N adju...

Page 80: ...rcentage given by A41 multi steps digital voltage 1000 bit DN adjustment mode of adjusting speed ratio 0 N adjustment of acceleration time No adjustment 1 AI1 adjustment of the external analog giving8...

Page 81: ...unction keys adjust the parameter values 2 MF is defined as a freedom stop function key Monitoring the menu Parameter select a menu of the key to effectively frequency inverter parking stopped parking...

Page 82: ...d potentiometer set 0 0 100 00 Y Displaying value potentiometer set which can be revised by potentiometer under monitor menu Value potentiometer set can be regarded as analog of frequency giving set v...

Page 83: ...isplaying value of motor temperature A5 surpassed value A52 inverter will warn and react according to reaction for motor over heat A53 set A54 Display of motor temperature8000 50 0 300 0 N Shows the m...

Page 84: ...100 0 Y o10 AI3 input X1 corresponding value Y18000 100 0 100 0 0 0 Y o11 AI3 input X2 corresponding value Y28000 100 0 100 0 100 0 Y Max frequency 50 00hz X1 0 Y1 0 potentiometer 0V corresponding set...

Page 85: ...00 X2 Y2 100 10V X1 Y1 5V 50 AI2 AI3jump as JP6 JP7 instruction as o12 AI1 input filter time 8000 o13 AI2 input filter time 0 00 2 00 s 0 10 Y o14 AI3 input filter time8000 0 00 2 00 s 0 10 Y Filter t...

Page 86: ...0 max frequency Actual current 3 0 200 corresponding parameter S03 percentage of output curent Output voltage 4 0 200 corresponding parameter b02 b15 rate voltage of motor DC bus voltage 5 0 1000VDC D...

Page 87: ...Fault warning 1 Over current inspection 2 Over load inspection 3 Over voltage inspection 4 Less voltage inspection 5 Low load inspection 6 Over heat inspection 7 Running state with command 8 Abnormal...

Page 88: ...or after fault with unconfirmed status 2 Over current inspeciton Inverter met fault of over current 3 Over load inspeciton Inverter met fault of over load of heat protection 4 Over voltage inspeciton...

Page 89: ...l at low pressure 27 Arrival of inverter rate current Arrival at inverter rate current 28 Arrival of motor rate current Arrival at motor rate current 29 Arrival of input frequency lower limitation Pre...

Page 90: ...ct After terminal reaction inverter will inspect FDT set frequency 2 When inverter output frequency is below of frequency 2 FDT set the corresponding signal output terminal will not react o31 frequenc...

Page 91: ...ning control 2 5 10bit Power on terminal running command invalid 0 Power on terminal running command valid 1 Setting terminal running mode by this parameter 1 bit set terminal running mode The polarit...

Page 92: ...level Falling edge Falling edge Falling edge Up edge Low level Falling edge Up edge Up edge X High level Up edge X 2 Two ware running control 1 FWD REV REV RUN STOP COM STOP FWD F05 1 F05 3 F05 4 Com...

Page 93: ...command invalid when power on Only run 3S later after power on and set terminals invalid 1 Terminal run command valid when Power on Terminal status is effective when power on inverter will run immedia...

Page 94: ...11 Multi digital voltage 2 12 Multi digital voltage 3 13 Frequency setting main way 1 14 Frequency setting main way 2 15 Frequency setting main way 3 16 Frequency setting assist way 1 17 Frequency se...

Page 95: ...2 switch 38 Free stop 39 Up command 40 Down command 41 Automatic program running function cancel 42 Automatic program running stop 43 Program running start mode 44 Program running stop mode 45 Pulse c...

Page 96: ...can set to edge trigger or level trigger 3 Three wire running STOP o35 set three wire running STOP function 4 Multistage speed command 1 Combine 16 step multi step setting Detail H parameter system 5...

Page 97: ...t switch Detail read C parameter system C16 30 REV torque up limit switch 2 31 REV torque up limit switch 3 32 Torque speed switch Vector control mode speed control mode and torque control mode switch...

Page 98: ...rt or stop Soft start control must use 2 terminal control stop priority Need to set E01 load model 9 E12 1pump is soft start control pump 52 1 pump stop 53 2 pump soft start Electric leverl spring con...

Page 99: ...0000 Y This parameter is used to select each IO pin polarity in which the effective 0 10 Input terminal polarity 12 15 Output terminal polarity 0 Low level valid closed 0 Low level valid closed Falli...

Page 100: ...id time 20ms 1 Output signal valid time 100ms 2 Output signal valid time 500ms 3 0 bit Counting mode of control 0 Recycle count the count value reaches maximum Pulse output to reach output terminal to...

Page 101: ...r status 0 9999 0 Y o54 Preset count value for a given 0 o55 0 Y o55 Max count value for a given o54 9999 9999 Y The correspondind indication of Yi terminal when input pulse signal count reach the pre...

Page 102: ...o63 SPA pulse output rate 1 1000 1 Y o64 SPB pulse output rate 1 1000 1 Y SPA SPB provide two isolated pulse output signal can be analogical multiple analog output signals SPA SPB provide high speed p...

Page 103: ...erved 100bit Reserved 1000bit Reserved 1 bit Timing mode 0 Boot time timing of runnig and breaking 1 Running timing only timing of running 10 bit Reserved 100 bit Reserved 1000 bit Reserved o67 Limit...

Page 104: ...t speed running 0 deceleration time decided by the H26 H39 1 The acceleration and deceleration time determined by terminal 1000 bit Set running time of defined program running 0 Running time decided b...

Page 105: ...t Single cycle 0 0000 Y Continuous cycle 1 One cycle command running 2 10 bit The zero speed running when pause 0 Fixed speed running when the suspension 1 100 bit Stop with the parameters set when st...

Page 106: ...0 bit Running condition when pause 0 Speed run when pause 1 Fixed Segment Speed operation when pause 100 bit Running Segment when stop 0 Set stopping according to the parameters of stop segment 1 Set...

Page 107: ...ed setting 2X Lower frequency upper frequency Hz 6 00 Y H05 3 Segment speed setting 3X Lower frequency upper frequency Hz 9 00 Y H06 4 Segment speed setting 4X Lower frequency upper frequency Hz 12 00...

Page 108: ...inal speed command 2 OFF OFF ON ON OFF OFF ON ON Multiterminal speed command 3 OFF OFF OFF OFF ON ON ON ON Multiterminal speed command 4 OFF OFF OFF OFF OFF OFF OFF OFF Speed Terminal 8X 9X 10X 11X 12...

Page 109: ...eleration time dt3 0 0 3200 0 s 10 0 Y H31 4 Segment acceleration time at4 0 0 3200 0 s 10 0 Y H32 4 Segment deceleration time dt4 0 0 3200 0 s 10 0 Y H33 5 Segment acceleration time at5 0 0 3200 0 s...

Page 110: ...me seconds 0 Running time munites 1 Running time hours 2 Running time days 3 100 bit Acceleration time seconds 0 Acceleration time munites 1 Acceleration time hours 2 Acceleration time days 3 1000bit...

Page 111: ...ent digital voltage giving 100 0 100 0 50 0 Y H53 6 Segment digital voltage giving 100 0 100 0 60 0 Y H54 7 Segment digital voltage giving 100 0 100 0 70 0 Y Digital voltage set function can analogy g...

Page 112: ...he third frequency value of V F curve corresponding to V3 U05 V F setting voltage 3 U03 U07 30 N User defined the third voltage percentage of V F curve on the base of rated output voltage 100 of frequ...

Page 113: ...ge Limited P00 PID configuration 1 bit Unidirectional regulation 0 0000 N Bidirectional regulation 1 10 bit Negative effect 0 Positive effect 1 100 bit PID fault No action 0 Warning continuous running...

Page 114: ...lection can select keyboard Rs485 potentiometer digital voltage digital pulse for feedback signal P03 Setting signal selection Set frequency by keyboard or RS485 0 2 Y AI1 external analogy giving 8000...

Page 115: ...n defines regulation intensity of PID regulator the larger the P is the more the intensity is When proportion gain is 100 and the difference between PID feedback and getting value is 100 PID regulator...

Page 116: ...sure water supply 9 Reserved 10 Reserved 11 Torque control 12 Voltage regulation power 13 Current regulation power 14 Extruding machine 15 Details see Appendix IV E01 Starting pressure deviation 0 0 1...

Page 117: ...nal select 25 then it will output arrival signal E06 Low pressure arrival value 0 100 0 10 0 Y When feedback pressure less than the low pressure of the reached value of this parameter the I O output t...

Page 118: ...ternation ways and time of pump When Timing Shift Alternation Time is set to 0 0 hour and cancel Timing Shift Alternation function When the Timing Shift Alternation Time between 0 1 3 200 after corres...

Page 119: ...No 2 pump No 3 pump If the current No 1 pump frequency No 2 pump frequency No 3 pump convert frequency after reduce pump No 1 pump frequency No 2 pump convert frequency after add pump 1 pump frequency...

Page 120: ...ault 13 E OHt Motor over heated fault 14 E OL2 Motor over loading fault 15 E PG PG fault 16 E PHo Inverter output Phase lost 17 E COA RS485 communication A fault 18 E COb RS485 communication B fault T...

Page 121: ...quency 1 Pump 1 run in working frequency 2 10 bit Pump 2 stop 0 Pump 2 run invariable frequency 1 Pump 2 run inworking frequency 2 100bit Pump 3 stop 0 Pump 3 run invariable frequency 1 Pump 3 run in...

Page 122: ...s unstable So it is necessary to consider the stability and the response speed at the same time when setting the value C01 Speed loop low speed Ti 0 01 100 00 s 0 25 Y It defines the integral time of...

Page 123: ...ibration if the gain is small the reaction lag C08 Speed Loop And High speed Switching Frequency C04 Max frequency Hz 30 00 Y It defines Integral time of speed loop high speed the parameter and switch...

Page 124: ...external analogy giving8000 3 Keypad potentiometer giving 4 Multi step digital 5 Digital pulse set 6 10bit direction Direction uncontrolled 0 Direction controlled 1 C17 Torque set gain 0 0 300 0 200 0...

Page 125: ...e both can control direction C15 0x14 C16 0x14 Potentiometer corresponding setting value A48 100 A49 100 Keyboard potentiometer set A47 100 C17 200 0 C13 forward upper torque 100 200 0 200 0 control d...

Page 126: ...2 torque acceleration time turning moment deceleration torque control mode and effective Torque acceleration time torque accelerated from 0 to 300 hours Torque speed torque from 300 down to 0 C23 Low...

Page 127: ...contact our company C31 PG dropped inspection time 0 0 10 0 s 1 0 N PG feedback signal is 0 exceed C31 set time system reports PG dropped fault Set speed to 0 or set C31 to 0 don t check PG dropped f...

Page 128: ...culates and measuresautomatically b05 b09 is the motor s basic electric parameters these parameters is essential to achieve vector control calculation b10 Motor selection Motor 1 0 0 N Motor 2 1 The s...

Page 129: ...et this parameter the motor parameters will be determined dynamically Be sure the motor is without load N load operation Before setting be sure to run well prepared the motor will run in high speed du...

Page 130: ...alue When this parameter set valid all the function parameter reset to factory setting The parameters without factory setting will save the previous setting value y01 Parameter upload to keyboard No a...

Page 131: ...OU Over voltage 5 E LU Under voltage 6 E OL Over load 7 E UL Under load warning 8 E PHI Power input Phase loss 9 E EEP EEPROM error 10 E ntC Over heat 11 E dAt Time limit fault 12 E Set External faul...

Page 132: ...temperat y08 Fault record reset No action 0 0 Y Reset 1 0 No action the fault records retains 1 The fault records resets y09 Rated output current 0 1 1000 0 A N Inverter rated output current y10 Rate...

Page 133: ...999 Set range Y No password or decode input is correct deco Display info Parameter lock in code The parameter sets the password and the range is 0 9999 After setting the password parameter locks and k...

Page 134: ...start after powering down or free run Remember the set operating state Too much load on the motor Check the load condtion and confirm the model selection is right Over current E OC Fault display E OC...

Page 135: ...line has too small capacity or great rush current exists on the lines Make renovation on power supply system Over heat E OHt Too high ambient temperature Improve ambient conditions Cooling fans do no...

Page 136: ...rter type Light Load F Standard Load G Structure item PF kW IF A PG kW IG A Single phase voltage 220V 50 60Hz PI8600 1 0 75 4 0 4 2 5 7N1 PI8600 1 1 5 7 0 75 4 7N1 PI8600 1 1 5 7 7N1 7 1 2 Table of ra...

Page 137: ...rate decelerate control Sub set S curve acceleration and deceleration mode maximum acceleration and deceleration time is 3200 days Long running time control 16 segments speed run maximum running time...

Page 138: ...inds of functions to achieve forward reverse forward jog and reverse jog emergency stop reset speed acceleration speed run time switch and pulse counting 1 way analog inputs Can be defined as a switch...

Page 139: ...wayl analog input pulse input digital potentiometers Motor 2 goups of motor parameters With the motor parameters parameter can be selected parameter identification automatic storage 3 identification...

Page 140: ...djust or inspect High voltage inside Maintained by the well trained personnel Confirm the input and output dc control cables are well connected Adjust or inspect the inner circuits after power down an...

Page 141: ...Section VII Standard Specifications 139 Section VII 7 3 2 Keyboard Size JP6C8000 Size...

Page 142: ...rd specifications Main circuit Body Input output terminal Main circuit Overall conditions If the fastenings come loose if any signs show overheat discharging or too high dust content or the air piping...

Page 143: ...ately after delivery to the user and need to keep well for the time being or stored for a long time Stored in a dry and adequately ventilated place without dust and metal powder at the temperature spe...

Page 144: ...face methods Asynchronism communication methods semi duplex the previous high byte low byte in the post and low effective bit pre emptive Data fumula 1 start bit 8 data bits 1 stop bit invalid parity...

Page 145: ...ight set communication parameters as following A29 baud rate 0 1200 1 2400 2 4800 3 9600 4 19200 5 38400 A28 current inverter communication address 1 127 If there are more than 1 inverters don t use t...

Page 146: ...ble and is linked to the signal terminal SH of RS485 Data packet using CRC vertical lengthy test frame detection to ensure data reliability Completely isolated RS485communication module to ensure reli...

Page 147: ...tart address Slave Address Function code Registers address Register number CRC Checksum Frame end address 3 5 bytes 1 bytes 1 bytes 2 bytes 2 bytes 2 bytes 3 5 bytes Slave response Frame Start address...

Page 148: ...ave address Function code Read byte number switch state CRC checksum frame end address 3 5bytes 1 byte 1 byte 1byte data N N bytes 2 bytes 3 5bytes Note read byte number N output quanlity 8 if the rem...

Page 149: ...0 71 H 0x03 0 55 U 0x04 0 15 P 0x05 0 15 E 0x06 0 23 C 0x07 0 47 b 0x08 0 23 yNOTE 1 0x09 0 23 S 0x0B 0 15 0x03 read inverter status Status Status number R 0x10 0x00 Running status NOTE 2 0x01 Reserve...

Page 150: ...and 2 0x03 Reserved command 3 Function parameter write EEPROM register address high byte original register address high byte 0x80 0x06 write inverter single function code parameter 0x10 write inverter...

Page 151: ...ower frequency 0 Lower frequency 1 Arrive 8 JOG running 0 No JOG running 1 JOG running 9 Reserved 10 Reserved 11 Reserved 12 Fault confirm 0 Confirmed fault 1 Unconfirmed fault 13 Direction status 0 N...

Page 152: ...Valid 10 AI3 input8000 0 Invalid 1 Valid Output terminal function 0x02 0 O1 input 0 Invalid 1 Valid 1 O2 input 0 Invalid 1 Valid 2 O3 input 0 Invalid 1 Valid 3 O4 input 0 Invalid 1 Valid Fault type 0x...

Page 153: ...or over load fault 19 E PG PG error 20 E PHo Inverter output phase loss 21 E COA Rs485 communication port A fault 22 E COb Rs485 communication port B fault 23 E CAL Parameter indentification fault 0x0...

Page 154: ...d 1 DI2 input 0 Invalid 1 Valid 2 DI3 input 0 Invalid 1 Valid 3 DI4 input 0 Invalid 1 Valid 4 DI5 input8000 0 Invalid 1 Valid 5 DI6 input8000 0 Invalid 1 Valid 6 DI7 input8000 0 Invalid 1 Valid 7 DI8...

Page 155: ...ltage Valid operation Invalid operation y11 products series 80 0 3 Invalid operation Family serial products series Input voltage level The number should be decimalization y12 soft ware version Valid o...

Page 156: ...e Reserve Reserve bit 7 bit 6 bit 5 bit 4 bit Meaning 0 No free stop 1 Free stop command Reserve 0 JOG stopping 1 JOG running Reserve bit 3 bit 2 bit 1 bit 0 bit Meaning Reserve 0 Reverse command 1 Fo...

Page 157: ...bit7 bit4 bit3 bit0 F 0 Forward command F 0 Forward status 0 Separative sign A 1 Accelerating running R 1 Reverse command R 1 Reverse status D 2 Decelerating running S 2 Stop command S 2 Stop status...

Page 158: ...yboard set frequency orRS485 Slave address Function code Read byte number Read content CRC checksum 0x08 0x03 0x04 0x1388 0x0000 0xE79D Read byte number 2byte register number 0x06 write inverter singl...

Page 159: ...number CRC checksum 0x08 0x01 0x0300 0x0020 0x3D0F Salve response inverter low voltage E LU switch address 0x0305 Slave address Function code Read byte number Switch state CRC checksum 0x08 0x01 0x04...

Page 160: ...ning and it can realize forced stopping by terminal or keyboard if need For this function the host computer should be set with the following parameters A28 Local communication address 128 For this fun...

Page 161: ...e and desist commands then the slave will respond the command again to run A28 communication address 1 127 A29 Baud rate Same as host A30 Communication format Same as host A55 Proportional linkage fac...

Page 162: ...he frequency or Rs485 0 F03 Auxiliary setting mode of frequency set AI2 external analog setting 1 F04 relationship between main and auxiliary frequencies main Auxiliary 2 F05 Running control mode Prop...

Page 163: ...Appendix II 161 Appendix II System wire connections...

Page 164: ......

Page 165: ...me time When speed up When speed down Failure Type OC OC P OC C OC FA OC 2 Abnorma l voltage OU LU OL UL Other display fault OH E FL PH O PID PG PG Error DATE use date expired EEPR EEPROM Board Failur...

Page 166: ...rvice faster and more convenient please visit our company web site http www powtran com and refer to column technologies and services and Download for feedback 1 download the updated manual for your p...

Reviews: