Section V Parameter Function Table
64
Sect
io
n
V
0 : Deceleration to stop
Mode converter according to parameters set by the deceleration time to set the deceleration
mode to slow down to the lowest frequencies to stop.
1 : Free stop mode
Inverter receive "stop" command immediately stop output, according to the load inertia,
motor free-run to stop.
F33
Jog acceleration time
0.0~3200.0
s
1.0
N
F34
Jog deceleration time
0.0~3200.0
s
1.0
N
F35
Jog mode setting
1 bit
Jog direction:forward
0
-
000
N
Jog direction:reverse
1
Jog direction: direction
determined by the main
terminal
2
10 bit
Jog end mode: stop running
0
Jog end mode:reset to the
former state before jog
1
100 bit
Jog end and acceleration
deceleration time: reset to
the set acceleration and
deceleration time before jog
0
Jog end and acceleration
deceleration time: save the
set acceleration and
deceleration time before jog
1
F36
Jog frequency setting
Lower frequency~upper frequency
Hz
6.00
Y
Jog acceleration/deceleration time configuration defines the same section of acceleration /
deceleration time.
The direction of jog is set by the unit bit of F35,when the Jog command does not contain the
direction of jog, the direction of job will run as to the unit bit designated by F35. It is set to 2, the
direction of jog is run by the terminal or current direction.
The running status after jogging is identified by F35.
Whether jog acceleration/deceleration time is maintained through the confirmation on
hundred bit of F35 after jogging.
F34
F33
running time
Linear Acceleration
Fmax
F37
Skip frequency1 limit
Skip frequency 1 limit
Hz
0.00
Y
F38
Skip frequency 1 upper
Skip frequency 1 upper
Hz
0.00
Y
F39
Skip frequency2 limit
Skip frequency 2 limit
Hz
0.00
Y