Section V Parameter Function Table
102
Sect
io
n
V
100 bit
Deceleration and
acceleration time
decised by H26~H39
0
Time of acceleration
and deceleration
isdecided by terminal
1
1000bit
Running time decised
by H18~H25
0
Running time decised
by terminal
1
1 bit: Program running functions intelligent
To use the program to run PLC functionality requires setting the bit to 1.
Multi-segment speed run only need to set the corresponding multi-stage o36 ~ o46-speed
switching can be used without the need to set this parameter.
0: Program running functions cancel
1: Program running function intelligent
10 bit: Define program runs or direction settings of multi-segment speed running
0: the direction decided by the H40 ~ H46
1: The directiondecided by the keyboard or terminal
100 bit:Define program runs or acceleration and deceleration time settings of multi-segment
speed running
0: deceleration time decided by the H26 ~ H39
1: The acceleration and deceleration time determined by terminal
1000 bit: Set running time of defined program running
0: Running-time decided by the H18 ~ H25
1: Running time decided by terminal
H01
Program running
configuration
1 bit
Sequence control
0
-
0710
Y
Terminal control
1
10 bit
Program running start
segment
0~15
100 bit
Program running end
segment
0~15
1000bit
Output signal valid time
8ms
0
Output signal valid time
20ms
1
Output signal valid time
100ms
2
Output signal valid time
500ms
3
1 bit: program run control mode
0: Sequential control
Run automatically according to the start segment,end segment and program running time of
program running.
You can use o36 ~ o46 switchover next function , switchover to the next program running .
1: Terminal control
Use multi segment control terminal o36 ~ o46 multi segment instruction 1, 2, 3, 4, Control
program segment, running time arrives,Running based on the 0 paragraph speed. After Multi
- stage speed control terminal switchover, reevaluate running time