Section V Parameter Function Table
84
Sect
io
n
V
Output RPM
8
Actual value of torque
9
o17
DA1 adjustment of lower
limit output
0.0~200.0
%
0.0
Y
o18
DA1 adjustment of upper
limit of output
0.0~200.0
%
100.0
Y
o19
DA2 adjustment of lower
limit output
8000
0.0~200.0
%
0.0
Y
o20
DA2 adjustment of upper
limit output
8000
0.0~200.0
%
100.0
Y
Output content
Setting value
Giving Output Singla Range
No reaction
0
No output
Setting frequency
1
0~max frequency
Actual frequency
2
0~max frequency
Actual current
3
0~200%, corresponding parameter: S03 percentage
of output curent
Output voltage
4
0~200%, corresponding parameter: b02
、
b15 rate
voltage of motor
DC bus voltage
5
0~1000VDC, DC voltage
IGBT temperature
6
0~100.0
℃
Output frequency
7
0~200%
Output speed
8
0~max speed
Real torque
9
0~200% torque
10V/20mA
10.0% 20.0%
the corresponded
output frequency
0V/0mA
50.0%
100.0%
0Hz
Voltage/Current
DA1
DA2
This parameter is used for setting upper/lower limitation of DA1/DA2 output signal.
Such as:
If DA1 output 1~5V voltage, setting parameter as: o17
=
10.0%, o18
=
50.0%
If DA2 output 4~20mA current, setting parameter as: o19
=
20.0%, o20
=
100.0%
DA1, DA2 Skipping thread:
: