Section V Parameter Function Table
127
S
ect
io
n
V
Keyboard figures area show "CAL1", inverter without output.
Keyboard figures area show "CAL2", inverter with output, static state.
Keyboard figures area show "-END": measuring ends.
Keyboard figures area show "E. CAL": the measurement process errors.
Process can be measured through the STOP key to stop.
3 : Inverter rotation measurement
Motor can be measured without load, can choose the rotation measurement. Measurements
started, make sure the motor is static.Static measurement converter, the output DC voltage,
pay attention to safety.
The b11 is set to 3, the inverter automatically start parameter determination.
Keyboard figures show that the regional show "-RUN": waiting to run the command, start
the measurement.
Keyboard figures area show "CAL1", "CAL3": N output inverter.
Keyboard figures area show "CAL2", inverter with output, under static state.
Keyboard figures area show "CAL4", inverter with output, the motor forward in high-speed.
Keyboard figures area show "-END": measuring the end.
Keyboard figures area show "E. CAL": the measurement process errors.
Process can be measured through the STOP key to stop.
Set this parameter,the motor parameters will be determined dynamically.Be sure the motor
is without load (N-load operation). Before setting,be sure to run well prepared,the motor will
run in high speed during the measurement
Measurement is completed, b11 return to 0. The measured parameters will select parameters
on the base of b10 motor parameters which is automatically saved to the b05 ~ b09 or b18 ~
b22.
Note
: Before auto-measure the motor parameter, must input motor rated parameter b00~b04
or b13~17 correctly
Please regulate accelerating and deceleration time or torque increasing parameter, if there is
over -current or over voltage faults while auto- measurement.
When automatic regulation, motor should be in stop status
b12
Vector control initial
inspection R1
Not inspection R1
0
-
0
N
Inspection R1
1
b13
Motor 2 rated frequency
0.00~Max frequency
Hz
50.00
Y
b14
Motor 2 rated current
y09*(50%~100%)
A
★
Y
b15
Motor 2 rated voltage
100~1140
V
★
Y
b16
Motor 2 pole pairs
1~8
-
2
Y
b17
Motor 2 rated speed
500~5000
rpm
1480
Y
b18
Motor 2 N load current
0.0~b14
A
★
Y
b19
Motor 2 stator resistance
0.000~30.000
ohm
★
Y
b20
Motor 2 rotator
0.000~30.000
ohm
★
Y
b21
Motor 2 stator inductance
0.0~3200.0
mH
★
Y
b22
Motor 2 mutual inductance
0.0~3200.0
mH
★
Y
The 2nd group motor parameters can be set by system. The definition is same with group 1.