Appendix I
Rs485 communication protocol
I-1.
Use introduction
This chapter introduces something about the install and handle of RS485 communication
between inverter and PLC, PC, factory computer.
●
Can communicate with all computer.
●
Using multi-drop link system, can link more to 127 inverters.
●
Completely isolated, and noise shield.
●
The user would use all types of RS232-485 inverter, if only the inverter had “automatic RTS
control” function inside.
I-2.
Specification
I-2-1.
Communication function
Items
Specification
Communication baud rate
38400/
19200
/9600/4800/2400/1200 bps is selectable.
Communication Protocol
Modbus protocol, RTU format
Interface methods
Asynchronism communication methods, semi-duplex, the previous
high byte, low byte in the post, and low-effective-bit pre-emptive.
Data fumula
1 start bit, 8 data bits, 1 stop bit, invalid parity bit.
Slave address
Slave addresses can be set up 1~ 127.0 for broadcast address, host
address 128 for the proportion of linkage, other addresses are reserved.
Communication port A
On-board keyboard (factory with standard), fixed 19200bps,
Please
do not change baud rate.
Isolation RS485 / RS232 communication card (optional), the default
19200bps.
Communication port B
RJ45, 8-core shielded cable, fixed 19200bps.
I-3.
Communication connection
I-3-1.
Connecting Communication port A
●
Connectting RS232 communication lines to frequency inverter control terminals row of RX232,
TX232
●
Connecting RS485 communication lines to frequency inverter control terminal row of (SG+) ,
(SG-)