58
NOTE 2:
U1-10 = X X
X
NOTE 3:
B2-01
B2-02
B2-03
B2-04
Constants
Model
Range
Unit
Factory
Setting
Range
Unit
Factory
Setting
Range
Unit
Factory
Setting
Range
Unit
Factory
Setting
PM-1500SI-122
180~230
1V
180V
181~260
1V
187V
240~269
1V
265V
230~270
1V
270V
PM-3000SI-122
180~230
1V
180V
181~260
1V
187V
240~269
1V
265V
230~270
1V
270V
PM-1500SI-242
180~230
1V
180V
181~260
1V
187V
240~269
1V
265V
230~270
1V
270V
PM-3000SI-242
180~230
1V
180V
181~260
1V
187V
240~269
1V
265V
230~270
1V
270V
PM-1500SI-121
94~120
1V
94V
95~135
1V
101V
128~142
1V
138V
120~143
1V
143V
PM-3000SI-121
94~120
1V
94V
95~135
1V
101V
128~142
1V
138V
120~143
1V
143V
PM-1500SI-241
94~120
1V
94V
95~135
1V
101V
128~142
1V
138V
120~143
1V
143V
PM-3000SI-241
94~120
1V
94V
95~135
1V
101V
128~142
1V
138V
120~143
1V
143V
B2-05
C1-01
C1-02
C1-03
Constant
Model
Range
Unit
Factory
Setting
Range
Unit
Factory
Setting
Range
Unit
Factory
Setting
Range
Unit
Factory
Setting
1500SI-122
1.0~16.0
0.1A
16.0A
210~245
1V
230V
9.3~13.0
0.01V
9.3V
10.9~17.0
0.01V
10.9V
3000SI-122
1.0~16.0
0.1A
160.A
210~245
1V
230V
9.3~13.0
0.01V
9.3V
10.9~17.0
0.01V
10.9V
1500SI-242
1.0~16.0
0.1A
16.0A
210~245
1V
230V
18.6~26.0
0.01V
18.6V
21.8~34.0
0.01V
21.8V
3000SI-242
1.0~16.0
0.1A
16.0A
210~245
1V
230V
18.6~23.0
0.01V
18.6V
21.8~34.0
0.01V
21.8V
1500SI-121
2.0~30.0
0.1A
30.0A
94~128
1V
120V
9.3~13.0
0.01V
9.3V
10.9~17.0
0.01V
10.9V
3000SI-121
2.0~30.0
0.1A
30.0A
94~128
1V
120V
9.3~13.0
0.01V
9.3V
10.9~17.0
0.01V
10.9V
1500SI-241
2.0~30.0
0.1A
30.0A
94~128
1V
120V
18.6~26.0
0.01V
18.6V
21.8~34.0
0.01V
21.8V
Aux-Relay3:
0=OFF
1=ON
Aux-Relay2:
0=OFF
1=ON
Aux-Relay1:
0=OFF
1=ON
Summary of Contents for PM-1500SI-12X
Page 17: ...17 Battery Shore Power Max 5A Load ATS ON AC IN AC OUT 5A 2A 30A 5A B2 05 5A 3A ...
Page 31: ...31 3 4 Battery Connection 3 4 1 Star Connection Schematic ...
Page 32: ...32 3 4 2 Rail Connection Schematic ...
Page 37: ...36 4 1 The following is the structure of user constants ...
Page 38: ...37 ...
Page 39: ...38 ...
Page 40: ...39 ...