75
production of an explosive gas.
Therefore, the charger is disabled if the bulk phase lasts more than 10 hours.
This setting can be disabled because it does not always indicate a problem when the bulk
phase lasts very long. The charge current can be very low due to limited AC input current
and/or AC loads. Also, DC loads can “steal away” part of the charge current. In that case,
the bulk phase will need more time to complete and this setting must be disabled.
※
Note: When this setting is disabled, there is no safety check against over-charging.
Setting
Function
D1-09=0
Stop After 10Hr Bulk setting is disabled
D1-09=1
(Initial setting)
Stop After 10Hr Bulk setting is enabled
D1-10: Equalize Mode Select (Storage Mode Select)
This setting is used for enabling/disabling the Equalize Mode.
In this mode, the voltage setpoint is 13.2V (for 12V battery). If Equalize mode is disabled,
then the normal float voltage will be used.
Setting
Function
D1-10=0
Equalize mode is disabled
D1-10=1
(Initial setting)
Equalize mode is enabled