77
E1-09: When bulk protection is activated.
This will set the Aux-Relay1 ON when the “bulk protection” (D1-09=1) is activated. This
condition will remain valid as long as the AC CHARGER is disabled due to that safety
mechanism. One can use this setting to generate an alarm.
E1-10: System Fault Occurs
This will switch on the Aux-Relay 1 when the Stackable Inverter switches off due to an
internal alarm situation.
E1-11: Temp. Alarm Select (When E1-12=0, ignore this setting)
E1-12: Temp. Alarm for ? sec
If you want to switch on the Aux-Relay 1 when there is a over temperature alarm, this
setting (E1-11) can be used to choose between pre-alarm or normal alarm.
As with other Aux-Relay 1 settings, a delay value (E1-12) must be specified also. This can
be done with Delay value for set Aux-Relay 1 ON when over temperature alarm (E1-12)
setting.
E1-13: Low Batt. Alarm Select (When E1-14=0, ignore this setting)
E1-14: Low Batt. Alarm for ? sec
If you want to switch on the Aux-Relay 1 when there is a low battery alarm, this setting
(E1-13) can be used to choose between pre-alarm or normal alarm.
As with other Aux-Relay 1 settings, a delay value (E1-14) must be specified also. This can
be done with Delay value for set Aux-relay 1 ON when low battery alarm (E1-14) setting.
E1-15: OverLoad Alarm Select (When E1-16=0, ignore this setting)
E1-16: OverLoad Alarm for ? sec
If you want to switch on the Aux-Relay 1 when there is a overLoad alarm, this setting
(E1-15) can be used to choose between pre-alarm or normal alarm.
As with other Aux-Relay 1 setting, a delay value (E1-16) must be specified also. This can
be done with Delay value for set Aux-Relay 1 ON when overload alarm (E1-16) setting.
E1-17: Udc Ripple Alarm Select (When E1-18=0, ignore this setting)
E1-18: OverLoad Alarm for ? sec
Summary of Contents for PM-1500SI-12X
Page 17: ...17 Battery Shore Power Max 5A Load ATS ON AC IN AC OUT 5A 2A 30A 5A B2 05 5A 3A ...
Page 31: ...31 3 4 Battery Connection 3 4 1 Star Connection Schematic ...
Page 32: ...32 3 4 2 Rail Connection Schematic ...
Page 37: ...36 4 1 The following is the structure of user constants ...
Page 38: ...37 ...
Page 39: ...38 ...
Page 40: ...39 ...