15
Chapter 2 Settings
Settings may only be changed by a qualified engineer.
Carefully read the user manual before any change is made.
When setting the charger, all connections to the battery must be disconnected from the
Stackable Inverter.
Do not use non-rechargeable batteries.
Batteries should be placed in a dry and well-ventilated area during charging.
The product default settings are for charging gel batteries. For the recommended battery
voltage initial settings, see D1 (Charger) Group parameters.
2.1 Four Control Modes Applications
MODE 1: AC Power as Priority Support (Example of
PM-3000SI
-242)
When Stackable Inverter enters to MODE 1, B2-09 (AC IN DynaCur Limit)=0 (Disable) and
the value of B2-18 (MODE1: ACINCurrent Lmt) will be loaded to B2-05.
1.
INVERTER Mode:
When AC IN=0 A, AC OUT load is completely supplied by INVERTER. It goes to the
inverter mode.
Battery
Grid,Shore,Generator
Power
Load
ATS OFF
AC IN
AC OUT
5A
5A
0A
75A