82
O Group (Operator):
O1 Group (Monitor Select)
O1-01: Power ON LCD Monitor Select
After power of the Stackable Inverter is on, the monitor selections will be showed on LCD
Display, U1-05 Battery Voltage is the initial display shown.
All the constants in U1 Group can be programmed (U1-01~U-26).
O1-02: Key Idle Detect Time
Use constant O1-02 to set the idle time when the keyboard is not operated and once any key
is pressed, the display will return to the LCD monitor selection value set in constant O1-01.
Initial Setting=180 sec, setting range: 10~600 sec.
O2 Group (Key Selections)
O2-01: Key Pressed Beep Select
Setting
Function
O2-01=0
When keys are pressed, beep sound will not be heard.
O2-01=1
(Initial setting)
When keys are pressed, beep sound will be heard.
O2-02: Elapsed Time Reset
Use constant O2-02 to reset elapsed time.
O2-03: Elapsed Time Select
Setting
Function
O2-03=0
(Initial setting)
The elapsed time started to be counted after power is on.
O2-03=1
The elapsed time started to be counted after RUN.
O2-04: Stackable Inverter Model
This is the model number to be displayed.