Wiring from
thermistor to logic
PCB faulty
YES
14.0 Fault Finding
42
When
fan ambient
temp < 90°C. Fan
protection stat open circuit ?
(measured at fan protection
thermostat)
Replace safety
thermostat (black)
Replace fan
protection stat.
Are
control PCB
safety thermostat
connections open
circuit ?
(H)
Wiring from control PCB
to safety or fan protection
thermostats faulty.
Replace flow
temperature
thermistor (red)
Is
combustion box door
seal damaged or not
in place ?
Replace combustion
box door seal.
Replace control PCB.
When
flow temp < 60°C.
Safety thermostat
open circuit ? (measured at
safety thermostat)
NO
YES
YES
NO
NO
NO
YES
YES
NO
Safety Lockout
Open
circuit across
thermistor
connections ?
Open
circuit
across thermistor
connections on
control PCB ?
Replace thermistor
YES
NO
NO
Thermistor Open Circuit
Is
flow temperature
thermistor resistance between
0.5k and 20k ? (measured
at flow temperature
thermistor)
Spark
Electrode
Ignition
PCB
Control
PCB
Condensate
Trap
Detection Electrode
Gas
Valve
Mains
Input
Optional
Pump Feed
Transformer
Overheat
Stat
Casing
Stat
Thermistor
Dry Fire
Flow Switch
DC
Fan
User PCB
br
br
w
g/y
g/y
br
b
b
b
b bk
br
bk
bk
bk
bk
bk
r
r
r
br
g
w
N P/F
bk
S/L
Pump
L
N
br
b
o o o o o o o o
g/y
br
r
b
bk
Earth
Electrode
H
Replace
control PCB