Potterton declare that no substances
harmful to health are contained in the
appliance or used during appliance
manufacture.
NOTE:
This appliance must be installed in
accordance with the manufacturer’s
instructions and the regulations in force, and
only used in a suitably ventilated location.
All systems must be thoroughly flushed
and treated with inhibitor (see Section 6.2).
Read the instructions fully before installing or
using the appliance.
1.1
Description
1. The Potterton Promax System HE is a gas
fired room sealed fan assisted condensing
central heating system boiler.
2. The maximum output of the boiler is preset at
75,000 Btu/hr. The boiler will automatically adjust
down to 30,000 Btu/hr according to the system
load. If required, the output can be set to 100,000
Btu/hr. Please refer to section 8.7.
3. It is designed for use on Natural Gas (G20).
4. The boiler is suitable for sealed central heating
and domestic hot water systems.
5. A label giving details of the model, serial
number and Gas Council number is situated on
the rear of the lower door panel (Fig. 1).
6. The boiler data badge is positioned on the air
box door (Fig. 2).
7. The boiler is intended to be installed in
residential / commercial / light industrial E.M.C.
environments on a governed meter supply only.
8. The boiler must be installed with one of the
purpose designed flues such as the standard
horizontal flue kit, part n
o
236921.
1.2
Optional Extras
KIT
PART N
o
FLUE EXTENSION KITS (110/70)
Flue Extension 0.25M
241692
Flue Extension 0.5M
241694
Flue Extension 1M
(Use two kits for 2M etc.)
241695
Flue Bend x 2 - 45°
(Reduce overall length of flue
by 0.5m when fitting this bend)
241689
Flue Bend - 90° (
Reduce overall length of flue
by 1m when fitting each bend)
241687
VERTICAL FLUE (110/70)
Vertical Flue Terminal
242802
Vertical Boiler Connection
242886
VERTICAL FLUE (80/80)
Kit Boiler Connection Twin
242757
1.0 Introduction
4
Fig. 1
Data Badge
Air Box Door
Lower Door Panel
Fig. 2
“Benchmark” Log Book
As part of the industry-wide “Benchmark” initiative all Potterton boilers now
include an Installation, Commissioning and Service Record Log Book.
Please read the Log Book carefully and complete all sections relevant to
the appliance and installation. These include sections on the type of
controls employed, flushing the system, burner operating pressure etc.
The details of the Log Book will be required in the event of any warranty
work. Also, there is a section to be completed at each subsequent regular
service visit.