1. Press button Operating mode button heating operation for approx 3 s
The message Controller stop active is displayed.
2. Wait until the display has reached the basic display again.
3. Press the Info button
The message Controller stop setpoint appears on the display. The
actual modulation degree will be displayed on the display.
4. Press OK.
The setpoint can now be changed.
5. Press OK.
The setpoint displayed is then adopted by the controller.
Important
The regulator stop function is stopped by pressing the operating
mode button Heating Operation for approximately 3 seconds,
reaching the maximum boiler temperature or a time limit.
If there is demand for heat from a coiled tubing storage tank, this
demand will continue to be met during the controller stop function.
7.4.7
Guidance values for gas flow rate, injector pressure and
CO
2
content
The values given in are for guidance. It is important that the gas quantity is
set via the injector pressure in such a way that the CO
2
value is within the
specified values.
If the Paramount is used in areas with fluctuating natural gas composition,
the CO
2
content must be adjusted in accordance with the Wobbe index at
any given time (ask the gas supply company).
The CO
2
content to be set can be decided as follows:
to Paramount 60: CO
2
content = 8,5 - (W
oN
- W
ocurrent
) * 0,5
over Paramount 60: CO
2
content = 8.8 - (W
oN
- W
ocurrent
) * 0,5
7.4.8
Guidance values for the gas flow rate
Tab.14 Guide values for the gas flow rate for natural gas
Model
Paramount
30
Paramount
40
Nominal input (full load)
kW
30
38
Gas flow rate
l/min
l/min
7
71
90
7.5
67
84
8
63
79
Operating heating value
8.5
59
74
H
uB
in kWh/m
3
9
56
70
9.5
53
67
10
50
63
10.5
48
60
11
45
58
11.5
43
55